KBW (E6) 11/2016
page 71/147
11.3 Resetting an alarm, list of active alarms
Normal display in state of alarm (example).
Press the
Alarm
icon
List of active alarms.
Press the
Reset alarm
icon.
Pressing the
Reset alarm
icon mutes the buzzer for all active alarms. The icon then disappears.
•
Acknowledging while the alarm condition persists: Only the buzzer turns off. The visual alarm indication
remains on the controller display. The alarm remains in the list of active alarms.
When the alarm condition has ended, the visual alarm indication is automatically cleared. The alarm is
then no longer in the list of active alarms.
•
Acknowledging after the alarm condition has ended: The buzzer and the visual alarm indication are
reset together. The alarm is then no longer in the list of active alarms.
•
The zero-voltage relay alarm output resets together with the alarm.
11.4 Tolerance range settings
In this menu you can set the deviation between the actual value and setpoint which that shall cause a
tolerance range alarm.
This function only activates after the set-point has been reached once.
Path:
Main menu > Settings > Various
Submenu “Various”.
Select the field “Range alarm delay”.
Entry menu “Range alarm delay”.
Enter the time in minutes, after which the range alarm
shall be triggered and press the
Confirm
icon.
Setting range: 15 min to 120 min.
Summary of Contents for KBW 240
Page 134: ...KBW E6 11 2016 page 134 147 23 7 Dimensions KBW 240 ...
Page 135: ...KBW E6 11 2016 page 135 147 23 8 Dimensions KBW 400 ...
Page 136: ...KBW E6 11 2016 page 136 147 23 9 Dimensions KBW 720 ...
Page 138: ...KBW E6 11 2016 page 138 147 ...
Page 140: ...KBW E6 11 2016 page 140 147 ...
Page 141: ...KBW E6 11 2016 page 141 147 25 Product registration ...