M 01/2009
page 26/61
8.
Manual Mode
In Manual Mode (HAND) you can enter a temperature set-point, the fan speed (0% to 100%), and the
switching-state of up to 8 operation lines. Operation line 1 is used to control the air flap position. The
other operation lines are non-functional. All settings remain valid for Manual Mode (HAND) until the next
manual change, also if the unit had been switched off or in case of toggling to Idle Mode or Program
Mode (AUTO).
8.1
Set-point entry
W
X
CONFIG
HAND
PGM
VIEW->
08:43:55 15.12.05
CONFIG
CONFIG
CONFIG
FAN
50.0
%
Idle Mode
No heating function.
Fan working at 50% rate (factory setting).
Toggling to Manual Mode
Change of page
08:43:55 15.03.05
HAND
HAND
Hand-Mode
TEMP
SPEED
Steuerkontakte
+29.3 °C
+80.0 %
Hand-Mode
TEMP
FAN SPEED
Operating contacts
+40.0 °C
+50.0 %
PGM
CONFIG
W
VIEW->
EXIT
Toggling between temperature set-point, fan speed, and operation lines.
08:43:55 15.12.05
HAND
08:43:55 15.12.05
Operating contacts
Contact 1
Contact 2
Contact 3
Contact 4
Contact 5
Contact 6
Contact 7
Contact 8
On
Off
Aus
Aus
Aus
Aus
Aus
Off
HAND
Contact 1
Off
On
Hand-Mode
TEMP
FAN
Oper
+40.0 °C
+80.0 %
TEMP
+0060.0
°C
EXIT
Arrow buttons to select the operation
lines
(Operation line 1 = air flap)
ON = air flap open
OFF = air flap closed
Arrow buttons
to enter the
value
Button to move the decimal point
Unlock the keyboard locking (option, chap. 11.3) via the key switch to enter the set-point.
Summary of Contents for APT.line M Series
Page 54: ...M 01 2009 page 54 61 15 6 Dimensions M 53 ENT ENT ENT...
Page 55: ...M 01 2009 page 55 61 15 7 Dimensions M 115 ENT ENT ENT...
Page 56: ...M 01 2009 page 56 61 15 8 Dimensions M 240 6 8 ENT ENT ENT...
Page 57: ...M 01 2009 page 57 61 15 9 Dimensions M 400 ENT ENT ENT...
Page 58: ...M 01 2009 page 58 61 15 10 Dimensions M 720 ENT ENT ENT...