MK LIT (E5) 01/2021
page 94/172
17.7 Value entry for a program section
Path:
Main menu > Programs > Time program
Select the desired program and section.
The section view gives access to all parameters of a program section. You can enter or modify the values.
Program name and section number
Section duration
Type of setpoint transition: ramp or step
Operation lines
Repeating one or several sections within a program
Temperature setpoint
Temperature tolerance range: minimum and maxi-
mum
The setting and control ranges for the individual parameters are the same as for “Fixed value” operating
mode (chap. 12).
17.7.1 Section duration
Section view (partial view).
Select the field “Duration” indicating the time.
“Duration” entry menu.
Enter the desired section duration with the arrow keys
and press the
Confirm
icon.
Setting range: 0 up to 99 hours 59 min 59 sec.