Installation, Operation and Maintenance Manual
VCIOM-01249-EN Rev. 0
81
View Routines
Section 10: View Routines
10.3
Valve Data
To identify the valve and its function in the process, the following data can be viewed:
•
Tag name (max. 28 characters)
•
Serial number (max. 28 characters)
•
Manufacturer (max. 28 characters)
•
Break OP torque (max. 28 characters)
•
Break CL torque (max. 28 characters)
•
Max stem thrust (max. 28 characters)
•
Flange type (max. 28 characters)
The data should be entered by the valve manufacturer or by the end user during
set-up operations.
View procedure
•
Move the local selector to OFF and then simultaneously press OPEN and STOP.
Select the language according to the instructions (see “Entering the view mode”).
When the message displayed is “VIEW MODE OK?” press YES. Press NO to scroll
the list of available menus and press YES to select the valve data menu.
•
Press YES to answer prompts “view” or “next” and see the data in the above list.
10.4
Maintenance
10.4.1
Alarm Log
The alarm log routine is used to view the list of the latest 5 alarms and 5 warnings and the
data when they occurred. The “clear alarm log” routine of the set-up menu should be used
to clear the list.
View procedure
•
Move the local selector to OFF and then simultaneously press OPEN and STOP.
Select the language according to the instructions (see “Entering the view mode”).
When the message displayed is “VIEW MODE OK?” press YES. Press NO to scroll
the list of available menus and press YES to select the Maintenance menu.
•
Press YES to answer the prompt “Alarm log view?”.
•
Press YES to scroll the list of alarms (“Alarms view?”).
•
Press NO to move on to “Warnings view?” and then YES to scroll the list
of warnings.