September 2021
Installation, Operation and Maintenance Manual
VCIOM-01249-EN Rev. 0
80
View Routines
Section 10: View Routines
10.2
Nameplate
Use this menu to view the data identifying the actuator. The data are entered in-house and
can only be changed by the manufacturer. The following data may be viewed:
•
Serial number: max. 28 characters, univocal identifier of the actuator by reference
to Biffi acknowledgment.
•
Actuator type: max. 28 characters, describes the type of actuator with reference to
Biffi catalog.
•
Torque / Thrust: nominal torque or thrust of actuator.
•
Actuator speed: nominal speed of actuator.
•
Power supply: nominal voltage and frequency of actuator.
•
Motor data: includes the following data relevant to the electrical motor:
—
Power type (3ph, 1ph, dc)
—
Power rating, max. 99.9 kW
—
In, max. 99.9 A
—
Is, max. 99.9 A
—
Icc, max 999.9 A
—
Duty (S2/15 min, etc.)
—
Poles (2, 4, etc.)
—
Biffi name, max. 28 characters
—
Gear ratio, max. 1000
•
Test date: date of the in-house functional test of actuator.
•
Wiring diagram (WD): wiring diagram number, max 28 characters.
•
Enclosure: type of enclosure (Ex d, etc.), max. 28 characters.
•
Certificate: number of certificate, max. 28 characters.
•
Lubricant: type of lubricant, max. 28 characters.
•
Revision: HW revision of base card, SW revision of H8 microprocessor, SW revision
of PIC microprocessor.
•
Torque sensor: data relevant to the relationship between motor torque and speed.
This set of data also includes the factory torque limit setting, “Torque set CL” and
“Torque set OP”.
View procedure
•
Move the local selector to OFF and then simultaneously press OPEN and STOP.
Select the language according to the instructions (see “Entering the view mode”).
When the message displayed is “VIEW MODE OK?” press YES. Press NO to scroll
the list of available menus and press YES to select the nameplate menu.
•
Press YES to answer the prompt “view” or “next” and see the data in the above list.