9.1.8 Fail-safe
This function configures the actuator action in case of loss of the 4 - 20 mA input or bus
signals. This action only takes place if the local selector is in REMOTE and if the positioning
function or the bus interface are active. When the 4 - 20 mA or bus signal is restored, the
F01-2000 resumes its normal functioning. The Interlock and ESD controls override the
fail-safe action according to Figure 47.
OP/CL controls
Lowest priority
Highest priority
Fail-safe action
Interlocks
ESD
Figure 47
Configuration procedure
•
Move the local selector to OFF and then simultaneously press OPEN and STOP.
Select the language and then enter the password according to the instructions
(see entering the set-up mode). When the message displayed is “SET-UP MODE
OK?” press YES. Press YES to select the actuator set-up menu, press NO to scroll
the list of available routines and then press YES to select FAIL-SAFE.
•
Press YES if the configured ACTION is correct (open, close, stay-put, go to position
xxx%, off), or press NO to change it, then press YES.
•
Press YES if the configured value of the DELAY is correct (from 0 to 255 s), or press
NO to change it, then press YES.
The following options can be configured:
•
- Action: open, close, stay-put, go to position %, no action (OFF).
•
- Delay: time before than the Fail-safe action takes place.