Biamp Vocia VO-4e Operation Manual Download Page 8

VO-4e Rear 

 

 

Failover is triggered by any of the following conditions:  

 

Chassis Fault  

 

Channel Fault  

 

Loss of power  

 

Loss of CobraNet link  

 

Loss of Failover Link Cable  

 

ELD-1 / speaker line Fault (if enabled in software)  

 

External amplifier Faults being asserted 

Only Chassis and Channel Faults trigger the Device failover mechanism. Abnormal conditions that do not 
immediately impair audio will appear as warnings but will not trigger failover. After a failover condition has 
been asserted, a power cycle of the units is required to recover from the failover. This can be done either 
by physically repowering the devices or by performing a ‘Device Reset’ in the Vocia software via the Test 
tab of the device dialog. The units are required to be reset within 10 seconds of each other in order to 
ensure the primary device resumes control.  

Channel-to-Channel Failover  

Channel-to-Channel failover is supported as 1:1 Channel. In this configuration, channel pairs can be 
specified and adjacent channels will act as a redundant backup. Channel 2 will act as backup for Channel 
1 and Channel 4 will act as backup for Channel 3. Channel failover is triggered by either a Channel 
Failure Fault, an ELD-1/Speaker Line Fault (if enabled in software) or an amplifier Fault Input being 
asserted. The VO-4e will return to normal operation after the Fault condition is cleared and the unit is re-
powered or reset via the Test tab in the Properties sheet.  

Summary of Contents for Vocia VO-4e

Page 1: ...VO 4e OPERATION MANUAL 585 0358 90C JANUARY 2016...

Page 2: ...lume control ducking equalization compressor limiter speaker crossover delay and output gain Emergency messages for life safety systems are stored in non volatile memory Two RJ45 connectors on the rea...

Page 3: ...plied by this manual relates to physical connections and assignment For more details on software setup please consult the Vocia Help File Installation The unit requires one 1 75 inch 44 45 mm high and...

Page 4: ...A solid green LED indicates that the unit is configured A flashing yellow LED indicates the unit is active but unconfigured A solid yellow LED indicates the unit is configured and in standby Standby...

Page 5: ...ctory Default Device ID is 01 A Device ID of 00 is invalid and cannot be used To assign a Device ID of hex 07 leave the MSB switch on 0 and turn the LSB switch to 7 Device ID switches should be set us...

Page 6: ...separate Control Inputs are provided via a six way 0 2 5 08mm pluggable screw terminal block Each Control Input allows for an external voltage free contact closure to ground to assert a Control Input...

Page 7: ...e of shielded speaker cable is not supported Highly capacitive speaker lines or loads may prevent correct operation of the ELD detection system Legacy monitored speaker circuits that use capacitors an...

Page 8: ...r by performing a Device Reset in the Vocia software via the Test tab of the device dialog The units are required to be reset within 10 seconds of each other in order to ensure the primary device resu...

Page 9: ...d Impedance 2k Maximum Output Level 22dBu Nominal Output Level 10dBu 0dBu or 4dBu Environment Ambient Operating Temperature 32 113 F 0 42 C Humidity 0 95 Altitude 0 10000 Feet MSL 0 3000 Meters MSL Co...

Page 10: ...Notes Page...

Page 11: ...Notes Page...

Page 12: ...Notes Page...

Page 13: ...t comply with all local codes National Electrical Code ANSI NFPA 70 for United States Canadian Electrical Code Part 1 CSA C22 1 Sections 2 128 12 010 3 and 12 100 for Canada Wall Mounting Instructions...

Page 14: ...ente o si se ha ca do ADVERTENCIA Para reducir el riesgo de incendio o descarga el ctrica no exponga estos productos a la lluvia o humedad Estos productos no deben exponerse a goteos o salpicaduras ni...

Page 15: ...position du produit l humidit ou la pluie fonctionnement anormal du produit chute du produit etc AVERTISSEMENT Pour limiter les risques d incendie ou d lectrocution n exposez pas ce produit l humidit...

Page 16: ...Umgebung gestanden ist sich nicht erwartungsgem verh lt oder wenn es gefallen ist ACHTUNG Um das Risiko eines Brandes oder eines elektrischen Schlages zu vermeiden das Ger t vor Regen und Feuchtigkeit...

Page 17: ...1 2 3 4 5 6 7 8 9 10 11 12 13 14 100 POTS 26 AWG Biamp Biamp ANSI NFPA 70 1 CSA C22 1 2 128 12 010 3 12 100 4 2...

Page 18: ...1 2 3 4 5 6 7 8 9 10 11 12 13 14 100 V Hazardous Live MAINS MAINS MAINS MAINS POTS 26 AWG Biamp Biamp AC MAINS ANSI NFPA 70 Part 1 CSA C22 1 Sections 2 128 12 010 3 12 100 4 2 2...

Page 19: ...Fuses 1 2 3 4 5 6 7 8 9 10 11 12 13 14 100 12 100 12 010 2 128 1 4 POTS AWG 26 Biamp Biamp Drywall ANSI NFPA 70 CSA C22 1 3...

Page 20: ...perar normalmente ou se tiver ca do AVISO Para reduzir o risco de inc ndio ou choque el trico n o exponha esses produtos chuva ou umidade Estes produtos n o devem ser expostos a goteiras ou respingos...

Page 21: ...1 2 3 4 5 6 7 8 9 10 11 12 13 14 100 POTS 26 AWG Biamp Biamp ANSI NFPA 70 1 CSA C22 1 2 128 12 010 3 12 100 4 2 1 5...

Page 22: ...ommercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instruction manual may cause harmful interference to rad...

Page 23: ...is presented to comply with Chinese law SJ T11363 2006 Hazardous Substances Table Biamp Systems Corporation Audio Output Device Vocia VO 4e Part Name Substances Pb Hg Cd Cr 6 PBB PBDE Equipment Chassi...

Page 24: ...ll become the property of Biamp Systems 4 This warranty will be VOID if the serial number has been removed or defaced or if the product has been altered subjected to damage abuse or rental usage repai...