BFT VIRGO SMART BT A Installation Manual Download Page 21

D812939 00096_03

46 

- VIRGO SMART BT A

INSTALLATION MANUAL

Logic

Definition

Default

Cross out

setting

used

Optional extras

iBL TCA

Block pulses during 

TCA 

0

0

Pulse from inputs configured as Start E, Start I, Ped has effect during TCA pause. 

1

Pulse from inputs configured as Start E, Start I, Ped has no effect during TCA pause. 

IBL CLOSE

Block pulses during 

closing 

0

0

Pulse from inputs configured as Start E, Start I, Ped has effect during closing. 

1

Pulse from inputs configured as Start E, Start I, Ped has no effect during closing. 

RAM BLOW 

C.OP

Hammer during 

opening

0

0

Logic not enabled

1

Before opening completely, the gate pushes for approx. 2 seconds as it closes. This allows the solenoid 

lock to be released more easily. 

IMPORTANT - Do not use this function if suitable mechanical stops are not in place.

RAM BLOW 

C.CL

Hammer during 

closing

0

0

Logic not enabled

1

Before closing completely, the gate pushes for approx. 2 seconds as it opens. This allows the solenoid lock 

to be released more easily. 

IMPORTANT - Do not use this function if suitable mechanical stops are not in place.

BLOC PER-

SIST

Stop maintenance

0

0

Logic not enabled

1

If motors stay idle in fully open or fully closed position for more than one hour, they are switched on in 

the direction of the stop for approx. 3 seconds. This operation is performed every hour.  

NB: In hydraulic motors, this function serves to compensate a possible reduction in the volume of oil due 

to a drop in temperature during extended pauses, such as during the night, or due to internal leakage. 

IMPORTANT - Do not use this function if suitable mechanical stops are not in place.

PRESS SWC

Closing limit switch 

pressure

0

0

Movement is stopped only when the closing limit switch trips: in this case, the tripping of the closing 

limit switch must be adjusted accurately (Fig.G Ref.B).

1

Use when there is a mechanical stop in closed position. 

This function allows leaves to press against the mechanical stop without the Amperostop sensor inter-

preting this as an obstacle. 

Thus the rod continues its stroke for a few seconds after meeting the closing limit switch or as far as the 

mechanical stop. In this way, the leaves come to rest perfectly against the stop by allowing the closing 

limit switches to trip slightly earlier (Fig.G  Ref.A).

ICE

Ice feature

0

0

The Amperostop safety trip threshold stays at the same set value.

1

The controller automatically adjusts the obstacle alarm trip threshold at each start up. 

Check that the force of impact measured at the points provided for by standard EN 12445 is lower than 

the value laid down by standard EN 12453. If in doubt, use auxiliary safety devices. 

This feature is useful when dealing with installations running at low temperatures. 

WARNING: once this feature has been activated, you will need to perform an autoset opening and closing 

cycle.

1  OT.ON

1 motor active

0

0

Both motors active (2 leaves).

1

Only motor 1 active (1 leaf).

change  ot

Reversal of the 

motor time lag

0

0

Opening: M1 starts in advance in comparison with M2 (opening time lag). (See Fig. J)

Closing: M2 starts in advance in comparison with M1 (closing time lag). (See Fig. J)

The pedestrian operation is performed by M1

1

Opening: M2 starts in advance in comparison with M1 (opening time lag). (See Fig. J)

Closing: M1 starts in advance in comparison with M2 (closing time lag). (See Fig. J)

The pedestrian operation is performed by M2

OPEN IN 

OTHER DI-

RECT.

Open in other 

direction

0

0

Standard operating mode (See Fig.J).

1

Opens in other direction to standard operating mode (See Fig. J)

SAFE 1

Configuration of 

safety input SAFE 1.  

72

0

0

Input configured as Phot (photocell). 

1

Input configured as Phot test (tested photocell).

2

Input configured as Phot op (photocell active during opening only).

3

Input configured as Phot op test (tested photocell active during opening only).

SAFE 2

Configuration of 

safety input SAFE 2.  

74

6

4

Input configured as Phot cl (photocell active during closing only).

5

Input configured as Phot cl test (tested photocell active during closing only).

6

Input configured as Bar, safety edge.

7

Input configured as Bar, tested safety edge.

8

Input configured as Bar 8k2.

9

Input configured as Bar OP, safety edge with inversion active only while opening. If while closing, the 

movement stops.

10

Input configured as Bar OP TEST, safety edge tested with inversion active only while opening. If while 

closing, the movement stops.

11

Input configured as Bar OP 8k2, safety edge with inversion active only while opening. If while closing, the 

movement stops.

12

Input configured as Bar CL, safety edge with inversion active only while closing. If while opening, the 

movement stops.

13

Input configured as Bar CL TEST, safety edge tested with inversion active only while closing. If while opening, 

the movement stops.

14

Input configured as Bar CL 8k2, safety edge with inversion active only while closing. If while opening, the 

movement stops.

IC 1

Configuration of 

command input IC 1.  

61

0

0

Input configured as Start E.

1

Input configured as Start I.

2

Input configured as Open.

3

Input configured as Close.

IC 2

Configuration of 

command input IC 2.  

62

4

4

Input configured as Ped.

5

Input configured as Timer.

6

Input configured as Timer Pedestrian.

Summary of Contents for VIRGO SMART BT A

Page 1: ...IRE AUTOMATIZACIONES A BRAZO PARA PORTONES CON BATIENTE AUTOMATIZA ES DE BRA O PARA PORT ES DE BATENTE Attenzione Leggere attentamente le Avvertenze all interno Caution Read Warnings inside carefully...

Page 2: ...an eye on the roller shutter while it is moving and keep peopleawayuntilithasclosedcompletely Exercise care when activating the release if such a device is fitted as an open shutter could drop quickly...

Page 3: ...E E click click 180 18 0 S ON OFF MANUALE D USO MANOVRA DI EMERGENZA USER GUIDE EMERGENCY OPERATION MANUEL D UTILISATION DE LA MANOEUVRE D URGENCE BEDIENUNGSHANDBUCH NOTFALLMAN VER MANUAL DE USO MANI...

Page 4: ...ekeyoperated must be installed at a height of at least 1 5 m and in a place where they cannot be reached by the public Apply at least one warning light flashing light in a visible position and also at...

Page 5: ...PA OL PORTUGU S DEUTSCH ITALIANO INSTALLAZIONE VELOCE QUICK INSTALLATION INSTALLATION RAPIDE SCHNELLINSTALLATION INSTALACI N R PIDA INSTALA O R PIDA A B 188 292 224 5 x 0 7 5 m m 2 5 x 0 7 5 m m 2 2 x...

Page 6: ...115 118 50 90 92 95 100 102 105 107 110 110 110 115 115 60 90 92 95 100 102 105 107 107 110 110 115 115 70 90 92 95 97 100 102 107 107 110 110 112 115 80 90 92 95 97 100 102 105 107 107 110 112 112 9...

Page 7: ...B 62 min 300 1 2 3 4 D E 25 MAX D o or ou oder o ou P D L F MAX M10 MAX L 25 mm Destra Right Droitea Rechts Derecha Direita Sinistra Left Gauche Links Izquierda Esquerda Non in dotazione Not supplied...

Page 8: ...M8 85 MAX M6 8 H Non in dotazione Not supplied Ne sont pas fournis Nicht im lieferum No asignadas en el equipamiento base N o fornecidas Non in dotazione Not supplied Ne sont pas fournis Nicht im lief...

Page 9: ...LEKTRISCHE VERRIEGELUNG aus Sicherheitsgr nden empfohlen FECHADURA EL TRICA recomendada por raz es de seguran a FECHADURA EL TRICA recomendada por raz es de seguran a 1x P 2x R 1x P 2x R 1x P 2x R 2x...

Page 10: ...a Pot ncia m xima 110W Ciclo massimo Maximum cycle Cycle maximum Max Zyklus Ciclo m ximo Ciclo m ximo 20 cycle h Con logica inversione direzione di apertura 000 DIR INT With reverse logic opening dire...

Page 11: ...otoc lulas no comprobadas para fotoc lulas comproabdas v anse las siguientes p ginas Conex o de 1 par de fotoc lulas n o verificadas para fotoc lulas verificadas consultar p ginas seguintes Alimentazi...

Page 12: ...em remotes end o o MIN 1 MAX 3 AUTO OPEN AUTO CLOSE Exit Men Confirm Switch on display Scroll up Scroll down ar automatic operation residential sr semiautomatic operation residential ac automatic oper...

Page 13: ...6 1 2 1 2 3 4 5 52 50 TX1 RX1 1 2 1 2 3 4 5 TX1 RX1 1 2 1 2 3 4 5 TX2 RX2 1 2 1 2 3 4 5 TX1 RX1 1 2 1 2 3 4 5 TX2 RX2 1 2 1 2 3 4 5 TX3 RX3 1 2 1 2 3 4 5 TX1 RX1 1 2 1 2 3 4 5 TX2 RX2 1 2 1 2 3 4 5 T...

Page 14: ...8 rst8 8888 1 2 3 4 6 5 3s UNIDA THALIA N O P ON OFF PROGRAMMATORE PALMARE UNIVERSALE UNIVERSAL PALMTOP PROGRAMMER PROGRAMMATEUR DE POCHE UNIVERSEL UNIVERSELLEN PALMTOP PROGRAMMIERER PROGRAMADOR DE BO...

Page 15: ...ge test failed Check safety edge connection and or logic settings ER03 Opening photocell test failed Check photocell connection and or parameter logic setting ER04 Closing photocell test failed Check...

Page 16: ...racket F to the leaf Insert the lever arm L into the output shaft of the gearmotor and secure it using the special pin P and the self locking nut D Release the actuator by operating the release lever...

Page 17: ...l connecting cables must be kept far enough away from the dissipater WARNING For connection to the mains power supply use a multicore cable with a cross sectional area of at least 3x1 5mm2 of the kind...

Page 18: ...not used leave jumper inserted SAFE logic 1 Input configured as Phot test tested photocell fig M ref 2 Switches photocell testing on at start of operation When beam is broken photocells are active du...

Page 19: ...emand wherenecessary editthemasdescribed in the programming section WARNING Check that the force of impact measured at the points provided for by standard EN 12445 is lower than the value laid down by...

Page 20: ...ening closing cycle is required WARNING When the display reads SET obstacle detection is not active Maintenance 0 250 0 Programming number of operations for maintenan ce threshold in hundreds Allows y...

Page 21: ...t measured at the points provided for by standard EN 12445 is lower than the value laid down by standard EN 12453 If in doubt use auxiliary safety devices This feature is useful when dealing with inst...

Page 22: ...ess memorizing of transmitters is disabled C Wireless automatic addition of clones is disabled D Wireless automatic addition of Replays is disabled E The option of editing the board s parameters via t...

Page 23: ...igured as Stair Light EXPO2 Configuration of EXPO2 output on input output expansion board 6 7 11 5 Output configured as Alarm 6 Output configured as Flashing light 7 Output configured as Latch 8 Outpu...

Reviews: