BFT VIRGO SMART BT A Installation Manual Download Page 17

D812939 00096_03

42 

- VIRGO SMART BT A

INSTALLATION MANUAL

 CONTROL PANEL

1) GENERAL INFORMATION

The 

THALIA

 control panel comes with standard factory settings. Any change 

must be made using the programmer with built-in display or universal handheld 

programmer. The Control unit completely supports the EELINK protocol.

Its main features are:   

-  Control of 1 or 2 24V BT motors

 

Note: 2 motors of the same type must be used.

-   Electronic torque control with obstacle detection

-   Limit switch control inputs based on motor selected

-  Separate inputs for safety devices

-   Built-in radio receiver rolling code with transmitter cloning.

The board has a terminal strip of the removable kind to make maintenance 

or replacement easier. It comes with a series of prewired jumpers to make the 

installer’s job on site easier.

The jumpers concern terminals: 70-71, 70-72, 70-74. If the above-mentioned 

terminals are being used, remove the relevant jumpers.

TESTING

The 

THALIA 

 panel controls (checks) the start relays and safety devices (photo-

cells) before performing each opening and closing cycle. 

If there is a malfunction, make sure that the connected devices are working 

properly and check the wiring.

2) TECHNICAL SPECIFICATIONS

Power supply

220-230V 50/60 Hz*

Low voltage/mains insulation

> 2MOhm 500V 

Operating temperature range

-20 / +55°C

Thermal overload protection

Software

Dielectric rigidity

mains/LV 3750V~ for 1 minute

Motor output current

max. 7.5A+7.5A

Motor relay switching current

10A

Maximum motor power

180W + 180W (24V  )

Accessories power supply

24V~ (demand max. 1A)

24V~safe

AUX 0

NO 24V  powered contact (max.1A)

AUX 3

NO contact (24V~/max.1A)

Fuses

see  

Fig. K

N° of combinations

4 billion

Max.n° of transmitters that can be memorized 63

(*other voltages to order)

Usable transmitter versions:

All ROLLING CODE transmitters compatible with 

2.1) VIRGO BAT BATTERY KIT (OPTIONAL)

3) TUBE ARRANGEMENT Fig.A

Arrange the electrical installation as shown in fig.A.

Keep the mains voltage connections definitely separate from the very low volt-

age connections (24V).

For this purpose, the operator is provided with appropriate fittings, indicated in Fig.A, 

for a spiral flexible raceway with an inside diameter of 20: 

- P1 input for mains power supply.

- P2/P3 inputs for safety devices and accessories.

For the mains power supply, use the appropriate cable clamp (Fig.A -”S”).

4) TERMINAL BOARD WIRING Fig.K

WARNINGS - 

When performing wiring and installation, refer to the standards in 

force and, whatever the case, apply good practice principles.

Wires carrying different voltages must be kept physically separate from each other, 

or they must be suitably insulated with at least 1mm of additional insulation. 

Wires must be secured with additional fastening near the terminals, using devices 

such as cable clamps.

All connecting cables must be kept far enough away from the dissipater.

WARNING! For connection to the mains power supply, use a multicore cable 

with a cross-sectional area of at least 3x1.5mm2 of the kind provided for 

by the regulations in force. To connect the motors, use a cable with a cross-

sectional area of at least 1.5mm2 of the kind provided for by the regulations 

in force. The cable must be type H05RN-F at least.

5) MOTOR CONNECTION AND LIMIT SWITCH ADJUSTMENT (Fig. J)

With the gate completely closed and open, rotate the corresponding cam until 

you hear the relevant limit microswitch click  and lock in position with the ap-

propriate screws.

Check the limit switches have activated correctly, starting some motorized open-

ing and closing complete cycles.

Terminal

Definition

Description

Po

w

er supply

L

LINE

Single-phase power supply 

220-230V 50/60 Hz*

N

NEUTRAL

JP5

TRANSF PRIM

Transformer primary winding connection, 220-230V.

JP7

JP21

TRANSF SEC

Board power supply:   

24V~ Transformer secondary winding  

24V= Buffer battery power supply

M

ot

or

10

MOT1 +

Connection motor 1. Time lag during closing.

Check connections shown in Fig.J

11

MOT1 -

14

MOT2 +

Connection motor 2. Time lag during opening.

Check connections shown in Fig.J

15

MOT2 -

Au

x

20

AUX 0 - 24V 

POWERED 

CONTACT  (N.O.)  

(MAX. 1A)

AUX 0 configurable output - Default setting FLASHING LIGHT. 

2ND RADIO CHANNEL/ SCA GATE OPEN LIGHT/ COURTESY LIGHT command/ ZONE LIGHT command/ STAIR LIGHT/ GATE OPEN 

ALARM/ FLASHING LIGHT/ SOLENOID LATCH/ MAGNETIC LOCK/ MAINTENANCE/ FLASHING LIGHT AND MAINTENANCE. Refer to 

“AUX output configuration” table.

21

26

AUX 3 - FREE 

CONTACT 

(N.O.)  

(Max. 24V 1A)

AUX 3 configurable output - Default setting 2ND RADIO CHANNEL Output. 

2ND RADIO CHANNEL/ SCA GATE OPEN LIGHT/ COURTESY LIGHT command/ ZONE LIGHT command/ STAIR LIGHT/ GATE OPEN 

ALARM/ FLASHING LIGHT/ SOLENOID LATCH/ MAGNETIC LOCK. 

Refer to “AUX output configuration” table.

27

Limit swit

ch 

for 

 

VIR

GO SM

ART 

BT A  5 wir

es

41

+ REF SWE

Limit switch common

42

SWC 1

Motor 1 closing limit switch SWC1 (N.C.).

43

SWO 1

Motor 1 opening limit switch SWO1 (N.C.).

44

SWC 2

Motor 2 closing limit switch SWC2 (N.C.).

45

SWO 2

Motor 2 opening limit switch SWO2 (N.C.).

Limit swit

ch f

or 

 

VIR

GO SM

ART 

BT A  3 wir

es

42

SW 1

Limit switch control motor 1.  

For actuators with single-wire limit switch control.

43

SW 2

Limit switch control motor 2.  

For actuators with single-wire limit switch control.

A

cc

essories

po

w

er supply

50

24V-

Accessories power supply output.

51

24V+

52

24 Vsafe+

Tested safety device power supply output (photocell transmitter and safety edge transmitter). 

Output active only during operating cycle.

Commands

60

Common

IC 1 and IC 2 inputs common

61

IC 1

Configurable command input 1 (N.O.) - Default START E. 

START E / START I / OPEN / CLOSE / PED / TIMER / TIMER PED 

Refer to the “Command input configuration” table.

62

IC 2

Configurable command input 2 (N.O.) - Default PED. 

START E / START I / OPEN / CLOSE / PED / TIMER / TIMER PED 

Refer to the “Command input configuration” table.

Summary of Contents for VIRGO SMART BT A

Page 1: ...IRE AUTOMATIZACIONES A BRAZO PARA PORTONES CON BATIENTE AUTOMATIZA ES DE BRA O PARA PORT ES DE BATENTE Attenzione Leggere attentamente le Avvertenze all interno Caution Read Warnings inside carefully...

Page 2: ...an eye on the roller shutter while it is moving and keep peopleawayuntilithasclosedcompletely Exercise care when activating the release if such a device is fitted as an open shutter could drop quickly...

Page 3: ...E E click click 180 18 0 S ON OFF MANUALE D USO MANOVRA DI EMERGENZA USER GUIDE EMERGENCY OPERATION MANUEL D UTILISATION DE LA MANOEUVRE D URGENCE BEDIENUNGSHANDBUCH NOTFALLMAN VER MANUAL DE USO MANI...

Page 4: ...ekeyoperated must be installed at a height of at least 1 5 m and in a place where they cannot be reached by the public Apply at least one warning light flashing light in a visible position and also at...

Page 5: ...PA OL PORTUGU S DEUTSCH ITALIANO INSTALLAZIONE VELOCE QUICK INSTALLATION INSTALLATION RAPIDE SCHNELLINSTALLATION INSTALACI N R PIDA INSTALA O R PIDA A B 188 292 224 5 x 0 7 5 m m 2 5 x 0 7 5 m m 2 2 x...

Page 6: ...115 118 50 90 92 95 100 102 105 107 110 110 110 115 115 60 90 92 95 100 102 105 107 107 110 110 115 115 70 90 92 95 97 100 102 107 107 110 110 112 115 80 90 92 95 97 100 102 105 107 107 110 112 112 9...

Page 7: ...B 62 min 300 1 2 3 4 D E 25 MAX D o or ou oder o ou P D L F MAX M10 MAX L 25 mm Destra Right Droitea Rechts Derecha Direita Sinistra Left Gauche Links Izquierda Esquerda Non in dotazione Not supplied...

Page 8: ...M8 85 MAX M6 8 H Non in dotazione Not supplied Ne sont pas fournis Nicht im lieferum No asignadas en el equipamiento base N o fornecidas Non in dotazione Not supplied Ne sont pas fournis Nicht im lief...

Page 9: ...LEKTRISCHE VERRIEGELUNG aus Sicherheitsgr nden empfohlen FECHADURA EL TRICA recomendada por raz es de seguran a FECHADURA EL TRICA recomendada por raz es de seguran a 1x P 2x R 1x P 2x R 1x P 2x R 2x...

Page 10: ...a Pot ncia m xima 110W Ciclo massimo Maximum cycle Cycle maximum Max Zyklus Ciclo m ximo Ciclo m ximo 20 cycle h Con logica inversione direzione di apertura 000 DIR INT With reverse logic opening dire...

Page 11: ...otoc lulas no comprobadas para fotoc lulas comproabdas v anse las siguientes p ginas Conex o de 1 par de fotoc lulas n o verificadas para fotoc lulas verificadas consultar p ginas seguintes Alimentazi...

Page 12: ...em remotes end o o MIN 1 MAX 3 AUTO OPEN AUTO CLOSE Exit Men Confirm Switch on display Scroll up Scroll down ar automatic operation residential sr semiautomatic operation residential ac automatic oper...

Page 13: ...6 1 2 1 2 3 4 5 52 50 TX1 RX1 1 2 1 2 3 4 5 TX1 RX1 1 2 1 2 3 4 5 TX2 RX2 1 2 1 2 3 4 5 TX1 RX1 1 2 1 2 3 4 5 TX2 RX2 1 2 1 2 3 4 5 TX3 RX3 1 2 1 2 3 4 5 TX1 RX1 1 2 1 2 3 4 5 TX2 RX2 1 2 1 2 3 4 5 T...

Page 14: ...8 rst8 8888 1 2 3 4 6 5 3s UNIDA THALIA N O P ON OFF PROGRAMMATORE PALMARE UNIVERSALE UNIVERSAL PALMTOP PROGRAMMER PROGRAMMATEUR DE POCHE UNIVERSEL UNIVERSELLEN PALMTOP PROGRAMMIERER PROGRAMADOR DE BO...

Page 15: ...ge test failed Check safety edge connection and or logic settings ER03 Opening photocell test failed Check photocell connection and or parameter logic setting ER04 Closing photocell test failed Check...

Page 16: ...racket F to the leaf Insert the lever arm L into the output shaft of the gearmotor and secure it using the special pin P and the self locking nut D Release the actuator by operating the release lever...

Page 17: ...l connecting cables must be kept far enough away from the dissipater WARNING For connection to the mains power supply use a multicore cable with a cross sectional area of at least 3x1 5mm2 of the kind...

Page 18: ...not used leave jumper inserted SAFE logic 1 Input configured as Phot test tested photocell fig M ref 2 Switches photocell testing on at start of operation When beam is broken photocells are active du...

Page 19: ...emand wherenecessary editthemasdescribed in the programming section WARNING Check that the force of impact measured at the points provided for by standard EN 12445 is lower than the value laid down by...

Page 20: ...ening closing cycle is required WARNING When the display reads SET obstacle detection is not active Maintenance 0 250 0 Programming number of operations for maintenan ce threshold in hundreds Allows y...

Page 21: ...t measured at the points provided for by standard EN 12445 is lower than the value laid down by standard EN 12453 If in doubt use auxiliary safety devices This feature is useful when dealing with inst...

Page 22: ...ess memorizing of transmitters is disabled C Wireless automatic addition of clones is disabled D Wireless automatic addition of Replays is disabled E The option of editing the board s parameters via t...

Page 23: ...igured as Stair Light EXPO2 Configuration of EXPO2 output on input output expansion board 6 7 11 5 Output configured as Alarm 6 Output configured as Flashing light 7 Output configured as Latch 8 Outpu...

Reviews: