INSTALLATION MANUAL
TABLE “A” - PARAMETERS MENU - (
PARA
)
Parameter
min. max. Default
Personal
Definition
Description
OPEN DELAY
TI E
0
10
3
Motor 2 opening delay
time [s]
Motor 2 opening delay time with respect to motor 1.
CLS DELAY
TI E
0
25
3
Motor 1 closing delay
time [s]
Motor 1 closing delay time with respect to motor 2.
TCA
0
120
10
Automatic closing time
[s]
Waiting time before automatic closing.
TRF.LGHT.CLR.T
1
180
40
Time-to-clear traffic light
zone [s]
Time-to-clear for the zone run through by traffic controlled by the traffic light.
OP.DIST.SLOUD
0
50
10
Slow-down distance
during opening [%]
Slow-down distance for motor(s) during opening, given as a percentage
of total travel. WARNING: Once the parameter has been edited, a
complete uninterrupted opening-closing cycle is required.
WARNING: when the display reads “SET”, obstacle detection is not active.
CL.DIST.SLOUD
0
50
10
Slow-down distance
during closing [%]
Slow-down distance for motor(s) during closing, given as a percentage
of total travel. WARNING: Once the parameter has been edited, a
complete uninterrupted opening-closing cycle is required.
WARNING: when the display reads “SET”, obstacle detection is not active.
DIST.DECEL
0
50
15
Deceleration distance
[%]
Deceleration distance (switch from running speed to slow-down
speed) for motor(s) both during opening and during closing, given as a
percentage of total travel. WARNING: Once the parameter has been
edited, a complete uninterrupted opening-closing cycle is required.
WARNING: when the display reads “SET”, obstacle detection is not active.
OP.FORCE
1
99
50
Leaf force during
opening [%]
Force exerted by leaf/leaves during opening. This is the percentage of force
delivered, beyond the force stored during the autoset cycle (and subsequently
updated), before an obstacle alarm is generated.
The parameter is set automatically by the autoset function.
WARNING: It affects impact force directly: make sure that current
safety requirements are met with the set value (*). Install anti-
crush safety devices where necessary (**).
CLS.FORCE
1
99
50
Leaf force during
closing [%]
Force exerted by leaf/leaves during closing. This is the percentage of
force delivered, beyond the force stored during the autoset cycle (and
subsequently updated), before an obstacle alarm is generated.
The parameter is set automatically by the autoset function.
WARNING: It affects impact force directly: make sure that current
safety requirements are met with the set value (*). Install anti-
crush safety devices where necessary (**).
OP SPEED
15
99
99
Opening speed [%}
Percentage of maximum speed that can be reached by motor(s) during
opening. WARNING: Once the parameter has been edited, a complete
uninterrupted opening-closing cycle is required. WARNING: when the
display reads "SET", obstacle detection is not active.
CL SPEED
15
99
99
Closing speed [%]
Percentage of maximum speed that can be reached by motor(s) during
closing. WARNING: Once the parameter has been edited, a complete
uninterrupted opening-closing cycle is required. WARNING: when the
display reads "SET", obstacle detection is not active.
SLOW SPEED
15
99
25
Slow-down speed [%]
Opening and closing speed of motor(s) during slow-down stage, given as a
percentage of maximum running speed. WARNING: Once the parameter has
been edited, a complete uninterrupted opening-closing cycle is required.
WARNING: When the display reads “”SET””, obstacle detection is not active.
(*) In the European Union, apply standard EN 12453 for force limitations, and standard EN 12445 for measuring method.
(**) Impact forces can be reduced by using deformable edges.
34 -