INSTALLATION MANUAL
TABLE “A” - PARAMETERS
TRIMMER
Parameter
+
min.
+
max.
Description
T1
Automatic
closing time [s]
0
120
Waiting time before automatic closing.
NOTE: Set to 0 if not used.
T2
Leaf force [%]
0
99
Force exerted by leaf/leaves.This is the percentage of force delivered, beyond the force stored during the
autoset cycle (and subsequently updated), before an obstacle alarm is generated.
WARNING: It affects impact force directly: make sure that current safety requirements are met
with the set value (*). Install anti-crush safety devices where necessary.
(*) In the European Union, apply standard EN 12453 for force limitations, and standard EN 12445 for measuring method.
TABLE “B” - LOGICS
DIP
Logic
Default
Cross out
setting used
Description
1
Photocells
during opening
OFF
ON
In the event beam is broken, photocell operation is disabled during opening. During closing,
movement is reversed immediately.
OFF
When beam is broken, photocells are active during both opening and clo-
sing. When beam is broken during closing, movement is reversed only once the
photocell is cleared.
2
Block pulses
during opening
OFF
ON
The start pulse has no effect during opening.
OFF
The start pulse has effect during opening.
3
3-step logic
OFF
ON
Switches to 3-step logic; during closing, start
reverses movement.
3 step
4 step
CLOSED
opens
opens
DURINg CLOSINg
stop
OPEN
closes
closes
DURINg OPENINg
stop +
TCA
stop +
TCA
AFTER STOP
opens
opens
OFF
Switches to 4-step logic.
4
Transmitter
programming
OFF
ON
Enables wireless memorizing of transmitters:
1- Press in sequence the hidden key and normal key (T1-T2-T3-T4) of a transmitter that has already
been memorized in standard mode via the radio menu.
2- Press within 10 sec. the hidden key and normal key (T1-T2-T3-T4) of a transmitter to be memorized.
The receiver exits programming mode after 10 sec.: you can use this time to enter other new tran-
smitters.
This mode does not require access to the control panel.
IMPORTANT: Enables the automatic addition of new transmitters, clones and replays.
OFF
Disables wireless memorizing of transmitters.
Transmitters are memorized only using the relevant Radio menu.
IMPORTANT: Disables the automatic addition of new transmitters, clones and replays.
5
1 Motor active
OFF
ON
Only motor 2 active (1 leaf).
OFF
Both motors active (2 leaves).
6
Reversing
motion
OFF
ON
Reverses the motion of motors with respect to standard operating mode: the rod comes out
during opening; the rod returns during closing.
OFF
Standard operating mode: the rod returns during opening; the rod comes out during closing.
LED INDICATORS:
POWER
Steadily lit: - Mains power on - Board powered - Fuse F1 intact
START
Lit:
- START input activated
- Radio receiver 1st channel activated
OPEN
Lit: OPEN pedestrian input activated
STOP
Unlit: STOP input activated
PHOT
Unlit: PHOT photocell input activated
Flashing: no photocell connected.
SW1
Unlit: motor 1 limit switches are disengaged
Lit: one of motor 1 limit switches is Engaged (leaf 1 is either fully
closed or fully open)
SW2
Unlit: motor 2 limit switches are disengaged
Lit: one of motor 2 limit switches is Engaged (leaf 2 is either fully
closed or fully open)
ER
Unlit: no error
Lit: error in safety device test or anti-crush safety device tripped
Flashing: Thermal overload protection tripped
MOTOR
Unlit: motors Stopped (Off)
Lit: motors Moving (On)
RADIO
(GREEN)
Unlit: remote programming not active
Radio LED only flashing: Remote programming active, waiting for
hidden key.
Flashing in sync with Set LED: Transmitter deletion in progress
Lit: remote programming active, waiting for desired key.
SET
Lit: Set key pressed / Autoset completed successfully
Flashes three times: Autoset or search for mechanical stop in progress
Fast flashing: Autoset failed
Flashing in sync with Radio LED: Transmitter deletion in progress
10) CONNECTION DIAGRAM FOR SEVERAL PAIRS (MAX. 4) OF A-CELLULA FLX
PHOTOCELLS FIG.G)
11) ADJUSTMENT PROCEDURE
- Before turning the unit on, check electrical connections.
- Set the following parameters: Automatic Closing Time, motor force.
- Set the logics.
- Run the autoset function.
WARNING! Incorrect settings can result in damage to property and injury
to people and animals.
WARNING: Check that the force of impact measured at the points
provided for by standard EN 12445 is lower than the value laid down
by standard EN 12453.
For best results, it is advisable to run the autoset function with the motors
idle (i.e. not overheated by a considerable number of consecutive operations).
10 - A-CT BOARD SW