5.00 OPERATING PARAMETERS
NAME
MEANING
SETTING
(for PTC std)
SEt
Main Set Point
Range between «LoS» &
«HiS»
HYS
Thermostat differential
(hysteresis)
Range 0 … 10 °C
LoS
Minimum value for SET POINT
parameter
Range –50 … +100 °C
HiS
Maximum value for SET POINT
parameter
Range –30 … +154 °C
Act
Thermostat control action:
cold/heat
0: cold;
1: heat.
LoA
Low temperature alarm point
Range –50 … +100 °C
HiA
High temperature alarm point
Range –30 … +155 °C
Alr
Alarm mode of operation
0: disabled;
1: enables Hit;
2: enables Lot;
3: enables Hit & Lot.
OFS
Probe offset. Temp. correction
factor
Range –9.9 … +9.9 °C
dPt
Defrost pause time
Range 1 ... 254 (see “tis”)
ddt
Defrost duration time
Range 0 … 99 (see “tis”)
AcY
Anticycling time
Range 0 … 254 (see “tis”)
Adi
Alarm delay on power-on
Range 0 … 99 min
unt
Measure unit
0: Celsius
1: Fahrenheit
dio
Digital input
0 … 2 (optional)
tiS
Time scale of defrost and
anticycling
0: dPt [h], ddt [m], acy [s];
1: dPt [m], ddt [s], acy [s];
2: dPt [h], ddt [m], acy [m];
3: dPt [m], ddt [s], acy [m];
utd
Update time delay
Range 0 … 60 s
rES
Resolution
0: decimal;
1: unit.
St2
Set point 2 (dio - energy saving)
Limits between «LoS» &
«HiS»
7.00 PARAMETER DESCRIPTION
SEt – Main Set Point:
it’s the required temperature.
HYS - differential hysteresis:
the value that controls the
compressor/heater operation, moving the value of the set point in such a
way that the system does not oscillate.
LoS - low limit of set point:
a limit below which it is not possible to
move the set point value.
HiS - high limit of set point:
a limit above which it is not possible to
move the set point value.
Act - thermostat action:
describes the way by which the controller
manages the controlled variable. 0: direct/cold action, good for
refrigerating units, 1: inverse/heat action, usable for boiler units.
LoA - low operation point of alarm temperature:
a limit below which
the system goes in alarm and simultaneously the display shows «LoT».
HiA - high operation point of alarm temperature:
a limit above which
the system goes in alarm and simultaneously the display shows «Hit».
Alr - alarm mode of operation:
the high and low temperature alarms
can be enabled or disabled as required by the installer. The available
options are: 0 = all alarms disabled; 1 = only high temperature alarm
enabled; 2 = only low temperature alarm enabled; 3 = high and low
temperature alarms enabled.
OFS - offset of temperature:
it is the variation temperature added or
subtracted to the temperature measured by the probe to compensate for
any deviation from the real value.
dPt - defrost pause time:
it
is the time between the start of two
consecutive defrost actions (time cycle).
ddt - defrost duration time:
it is the duration of the defrost in each
cycle.
Set ddt=0 to disable any defrost action.
AcY - anticycling delay time:
it is the minimum time between two
successive maneuvers of the main relay (off – on cycle). It is also the
delay for the first activation of the relay at the start-up.
Adi - alarm delay initialization:
delay between the power-up of the
instrument and the arming of the alarms if enabled.
unt – Measure unit:
it switches the temperature unit between Celsius
and Fahrenheit.
dio - digital input mode operation:
(optional) no active.
tiS - scale times:
it switches the scale times of the dPt from hours to
minutes, ddt from minutes to seconds, acy from seconds to minutes and
vice versa.
utd – update time delay:
it sets the time delay between two display
refreshes.
rES - resolution:
it allows to display the measured value with decimal or
unitary resolution.
St2 – 2dary set point:
No active – it is useful for the energy saving
option, combined with the dio parameter.
6.00 ANOMALIES SIGNALING
MSG
CAUSE
OUTPUT
Lot
Measured temperature is
lower than «LoA»
The relay status
does not change.
The internal buzzer
will switch on.
HIt
Measured temperature is
higher than «HIA»
The relay status
does not change.
The internal buzzer
will switch on.
PrF
The probe input line is
open or short circuited
The relay will switch
off
ATEX Industries srl
ATEX Industries srl
ATEX Industries srl
ATEX Industries srl
Z.I. Ponte Rosso - Via Forgaria, 7
33078 S. Vito al Tagliamento – PN - Italy
Tel.: +39 0434 85183 r.a.
Fax: +39 0434 85338
web:
www.betaelectronics.it
RD31
Rev.: 07-07-2006
Cod.: 00990226
by ATEX