  5.00 OPERATING PARAMETERS 

 

NAME 

MEANING 

SETTING 

(for PTC std)

 

SEt  

Main Set Point 

Range between «LoS» & 
«HiS»  

HYS 

Thermostat differential 
(hysteresis) 

Range 0 … 10 °C 
 

LoS 

Minimum value for SET POINT 
parameter 

Range  –50 … +100 °C 
 

HiS 

Maximum value for SET POINT 
parameter 

Range –30 … +154 °C 
 

Act 

Thermostat control action: 
cold/heat 

0: cold;  
1: heat. 

LoA 

Low temperature alarm point 

Range –50 … +100 °C 

HiA 

High temperature alarm point 

Range –30 … +155 °C 

Alr 

Alarm mode of operation 

0: disabled; 
1: enables Hit; 
2: enables Lot; 
3: enables Hit & Lot. 

OFS 

Probe offset. Temp. correction 
factor 

Range –9.9 … +9.9 °C 
 

dPt 

Defrost pause time 

Range 1 ... 254 (see “tis”) 

ddt 

Defrost duration time 

Range 0 … 99 (see “tis”) 

AcY 

Anticycling time 

Range 0 … 254 (see “tis”) 

Adi 

Alarm delay on power-on 

Range 0 … 99 min 

unt 

Measure unit 

0: Celsius 
1: Fahrenheit 

dio 

Digital input 

0 … 2 (optional) 

tiS 

Time scale of defrost and 
anticycling 

0: dPt [h], ddt [m], acy [s]; 
1: dPt [m], ddt [s], acy [s]; 
2: dPt [h], ddt [m], acy [m]; 
3: dPt [m], ddt [s], acy [m]; 

utd 

Update time delay 

Range 0 … 60 s 

rES 

Resolution 

0: decimal; 
1: unit. 

St2 

Set point 2 (dio - energy saving) 

Limits between «LoS» & 
«HiS» 

  

7.00 PARAMETER DESCRIPTION 

 

SEt – Main Set Point:  

it’s the required temperature.

 

HYS  -  differential  hysteresis:

  the  value  that  controls  the 

compressor/heater operation, moving the value of the set point in such a 
way that the system does not oscillate. 

LoS  -  low  limit  of  set  point: 

a  limit  below  which  it  is  not  possible  to 

move the set point value. 

HiS  -  high  limit  of  set  point: 

a  limit  above  which  it  is  not  possible  to 

move the set point value. 

Act  -  thermostat  action: 

describes  the  way  by  which  the  controller 

manages  the  controlled  variable.  0:  direct/cold  action,  good  for 
refrigerating units, 1: inverse/heat action, usable for boiler units. 

LoA  -  low  operation  point  of  alarm  temperature:

  a  limit  below  which 

the system goes in alarm and simultaneously the display shows «LoT». 

HiA - high operation point of alarm temperature:

 a limit above which 

the system goes in alarm and simultaneously the display shows «Hit». 

Alr  -  alarm  mode  of  operation: 

the  high  and  low  temperature  alarms 

can  be  enabled  or  disabled  as  required  by  the  installer.  The  available 
options  are:  0  =  all  alarms  disabled;  1  =  only  high  temperature  alarm 
enabled;  2  =  only  low  temperature  alarm  enabled;  3  =  high  and  low 
temperature alarms enabled. 

OFS  -  offset  of  temperature:

  it  is  the  variation  temperature  added  or 

subtracted  to the temperature measured by the probe to compensate for 
any deviation from the real value. 

dPt  -  defrost  pause  time:

    it

 

is  the  time  between  the  start  of  two 

consecutive defrost actions (time cycle). 

ddt    -  defrost  duration  time:

  it  is  the  duration  of  the  defrost  in  each 

cycle. 

Set ddt=0 to disable any defrost action. 

AcY  -  anticycling  delay  time: 

it  is  the  minimum  time  between  two 

successive maneuvers   of  the main relay  (off  – on cycle). It is  also the 
delay for the first activation of the relay at the start-up. 

Adi  -  alarm  delay  initialization: 

delay  between  the  power-up  of  the 

instrument and the arming of the alarms if enabled. 

unt  –  Measure  unit:

  it  switches  the  temperature  unit  between  Celsius 

and Fahrenheit. 

 

dio - digital input mode operation:

 (optional) no active. 

tiS  -  scale  times: 

it  switches  the  scale  times  of  the  dPt  from  hours  to 

minutes, ddt from minutes to seconds, acy from seconds to minutes and 
vice versa. 

utd  –  update  time  delay:

  it  sets  the  time  delay  between  two  display 

refreshes. 

rES - resolution:

 it allows to display the measured value with decimal or 

unitary resolution. 

St2  –  2dary  set  point: 

No  active  –  it  is  useful  for  the  energy  saving 

option, combined with the dio parameter. 

    6.00 ANOMALIES SIGNALING

 

MSG 

CAUSE 

OUTPUT 

Lot 

Measured temperature is 
lower than «LoA» 

The relay status 
does not change. 
The internal buzzer 
will switch on. 

HIt 

Measured temperature is 
higher than «HIA» 

The relay status 
does not change. 
The internal buzzer 
will switch on. 

PrF 

The probe input line is 
open or short circuited 

The relay will switch 
off 

 

ATEX Industries srl

ATEX Industries srl

ATEX Industries srl

ATEX Industries srl    

Z.I. Ponte Rosso - Via Forgaria, 7 

33078 S. Vito al Tagliamento – PN - Italy 

Tel.: +39 0434 85183 r.a. 

Fax: +39 0434 85338 

web:

 www.betaelectronics.it 

e-mail

[email protected]

 

 
 

 
 

RD31 

Rev.: 07-07-2006 
Cod.: 00990226

 

 

by ATEX 

 

 

Reviews: