UT340, UT360, UT380, and UT3100
Planning and Installation Manual
33
4. Turn the pre-charge/discharge switch to the pre-charge position and hold it until the LED
turns off.
5. Switch the DC disconnect (DCD) “ON.”
6. Press the green “on” button located inside the UPS front door. The UPS display should show
Normal operation load power xx%
.
7. Program the UPS into static bypass operation:
a. Press to access the user parameters.
b. Press the or key until the display shows
Bypass operation: OFF
.
c. Press to turn bypass operation on. The display should show
Bypass
operation
.
8. Switch the UPS output breaker (UOB) “ON.”
9. Switch the maintenance bypass breaker (MBB) “OFF.”
10. Program the unit to normal operation:
a. Press to access the user parameters.
b. Press the or key until the display shows
Bypass operation: ON
.
c. Press to switch the bypass operation off. The display should show
Normal
operation load power xx%
.