BESANTEK
- - - - -
-
Select the Positive or Negative
Start Edge using the Select Button.
Connect Leads
to Earth & Phase
Connect Leads to Earth and Phase.
Testing will start Automatically when voltage is detected.
I
V=317V
I
I=127mA
Test In Progress. The Voltage between leads was 317V
before testing started and I=127mA
V=317V
1=140mA Hold➔ TRP
TRP
= Tripped, Display on Hold
Tripped at 140mA, on - edge of signal.
Determination of the disconnection time of the Earth Leakage
Circuit Breaker
Connect the Earth lead from the tester to the Earth connection on
the system. Using the rotary switch, select which phase you want to
test from, connect the phases.
Turn Instrument "ON" by pressing the "TEST-ON" button.
The L.C.D. display will come to the following Screen.
* -
Instantaneous
--◄•►
- Time Delay
Push Select to change Selection
to Instantaneous, then Press "TEST" to accept.
Dial Starting
Current. 125mA
-7-