Automation PC 820 User's Manual V 1.20
2.6.6 Serial interface COM2
I/O address and IRQ
The setting for the I/O address and the IRQ can be changed in the BIOS setup (under
"Advanced" - submenu "Baseboard/Panel Features" - submenu "Legacy Devices", setting "COM
B"). Please note any potential conflicts with other resources when changing this setting.
Bus length and cable type RS232
The maximum transfer rate of 115 kBit/s depends on the cable type being used.
Serial interface COM2
RS232
RS422/485
9-pin DSUB connector
Type
RS232 not modem compatible;
Electrically isolated
UART
16550 compatible, 16 byte FIFO
Transfer rate
Max. 115 kBit/s
Bus length
Max. 15 m
Max. 1200 m
Pin
Assignments
(RS232)
Assignments
(RS422)
1
n.c.
TXD\
2
RXD
n.c.
3
TXD
n.c.
4
n.c.
TXD
5
GND
GND
6
n.c.
RXD\
7
RTS
n.c.
8
CTS
n.c.
9
n.c.
RXD
Table 22: Pin assignments - COM2
Resource
Default setting
Additional setting options
I/O address
2E8h
238, 2F8, 338, 3E8, 3F8
IRQ
IRQ10
IRQ 3, 4, 5, 7, 11, 12
Table 23: RS232/422/485 - I/O address and IRQ
Extension
Transfer rate
≤
15 m
typ. 64 kBit/s
≤
10 m
typ. 115 kBit/s
≤
5 m
typ. 115 kBit/s
Table 24: RS232 - Bus length and transfer rate
COM1
COM2
1
5
6
9
Summary of Contents for 5PC820.SX01-00
Page 2: ...2 Automation PC 820 User s Manual V 1 20...
Page 4: ...4 Automation PC 820 User s Manual V 1 20...
Page 6: ...6 Automation PC 820 User s Manual V 1 20...
Page 80: ...80 Technical data Individual components Automation PC 820 User s Manual V 1 20...
Page 108: ...108 Commissioning Known problems issues Automation PC 820 User s Manual V 1 20...
Page 304: ...304 Automation PC 820 User s Manual V 1 20 Figure index...
Page 310: ...Table index 310 Automation PC 820 User s Manual V 1 20...
Page 312: ...Model number index 312 Automation PC 820 User s Manual V 1 20 9S0000 01 020 26 193...