BERMAD 450-66-Z Maintenance Operation Installation Download Page 1

 

MODEL   

450-66-Z

 

BI LEVEL RESERVOIR FLOAT VALVE (with manual selector)

 

   INSTALLATION

   OPERATION

 MAINTENANCE

 

 

The information contained in this document is subject to change without notice. 
BERMAD shall not be liable for any errors contained herein. All Rights Reserved. © Copyright by BERMAD Control Valves. 

Page 1 

 
 

 

 

 

 

 

DESCRIPTION

 

Model 750-66 Bi-level Reservoir Control Valve is an 
automatic control valve designed for two-level 
control of the water level in reservoirs and tanks.  
Four-way operation enables full opening even at very 
low pressure.  Full valve opening reduces head loss 
to a minimum, prevents abrasion and reduces 
cavitation damage. The valve can be operated via an 
independent external pressure source when line 
pressure is very low, or when the water/liquid is very 
dirty or highly corrosive.

 

 

INSTALLATION

 

1. Allow enough room around the valve assembly for 
making adjustments and for future maintenance / 
disassembly work.

 

2. Thoroughly flush the pipeline to remove dirt, scale, 
and debris. Failure to perform this operation may render 
the valve inoperable.

 

3. Isolation valves A and B should be installed upstream 
and downstream of the Bermad control valve to allow 
future maintenance operations.

 

4. Install the valve in the pipeline with the valve flow 
arrow on the body casting in the proper direction. Use 
the lifting eye provided on the main valve cover for 
raising and lowering the valve. For best performance, 
install the valve horizontally with the cover up. Ensure 
that the valve is positioned so that the actuator assembly 
can be easily removed for future maintenance.

 

5. After installation carefully inspect /correct any 
damaged accessories, piping, tubing, or fittings.

 

 

ON LINE STATIC TEST PROCEDURES 

OPEN VALVE: STATIC TEST 

1. Turn cock valve #26 to open position.

 

Caution:

 This will allow the valve to open fully.  Make sure that 

this condition does not cause system damage. 
2. Check for leaks at the flange connection fittings etc.

 
 

CLOSED VALVE: STATIC TEST 

1. Turn cock valve #26 to close position, vent any trapped air in 
the main valve cover by loosening the tube fitting at the highest 
point on the cover. This will trap the main valve in a closed 
position while the pipeline is pressurized.

 

2. Check the valve cover and diaphragm area for leaks, tighten 
the actuator bolts where necessary.

 
 

START-UP OPERATION 

1. Close the main valve by closing cock valve #26 and lifting the 
float to the upper level. 

 

NOTE

: Isolating valves A and B should be open.

 

2. Check valve operation by lifting and dropping the float; the 
main valve should open and close.

 

3. If the main valve operating speed increases, fit a needle 
valve on either port V on the four-way float pilot or on the 
pressure hydraulic tube supply above filter 4. Adjust the needle 
valve until the desired flow speed is obtained.

 

4. Pilot adjustment: Install the pilot valve 66 to the reservoir 
wall, higher than the upper level (refer to the drawing). Remove 
the plastic float, loosen the counterweight locking screw (9) and 
balance the lever system horizontally by moving the 
counterweight to find the equilibrium.  After balancing, replace 
the float and tighten the counterweight locking screw.

 

5. Adjust the upper/lower water level by moving the float stops 
up/down (float while the float is held between the float stops).

 

6. The float control should be placed where the liquid surface is 
free from turbulence; where this is not possible, a stilling tank 
must be placed around the float to prevent it from swinging.

 

7. There should be adequate space between the reservoir wall 
and the float.

 

Reviews: