61
Help in case of trouble
GB
Manual control with keypad not possible
Cause 1: manual control mode not programmed.
Program the device for manual control.
Cause 2: manual control mode disabled from bus.
Enable the manual control mode.
Output control not possible
Cause 1: output disabled.
Re-enable the output.
No output operational
Cause 1: all outputs are disabled.
Re-enable the outputs.
Cause 2: permanent manual control mode active.
Deactivate the permanent manual control mode (switch this
mode off).
Cause 3: application software stopped, programming LED flashing.
Make a reset: disconnect the device from the bus, reconnect
after 5 seconds.