USER MANUAL 1.2 | B-NIMIS MC-PI AND BC-PI SERIES
Berghof Automation GmbH | Arbachtalstrasse 26 | 72800 Eningen | Germany | www.berghof-automation.com
38
7.3.4. Start/Stop reset button
This chapter applies only for the MC-Pi series!
The Reset/Stop button is located on the front of the device below the status LEDs.
To prevent unintentional operation, the Stop/Reset button can only be operated with a thin pointed
object (pen, screwdriver).
The functio
n depends on the controller’s current operating status
CODESYS Stop
– Start – Reset
A running CODESYS application is stopped by briefly pressing the button. The Run / Stop LED
changes from green to red. A second short press will start the CODESYS application. The Run /
Stop LED changes from red to green. If the button is pressed and held for more than 5 seconds, a
“Warm reset” is triggered. After the time has elapsed, the Run/Stop LED flashes quickly and the
button can be released. The controller is now in the reset state.
Service mode
The controller must be switched off to enter service mode. The button is then held down and the
controller is switched on again. The button must be kept pressed until the Run/Stop LED flashes
yellow every two seconds.