USER MANUAL 1.2 | B-FORTIS CC-PRIME SERIES
Berghof Automation GmbH | Arbachtalstrasse 26 | 72800 Eningen |
46
5.3.8. RS 485 interface
Fig. 20: RS 485 interface
Assignment RS 485 interface plug X9
Pin
Assignment
Pin
Assignment
1
NC
5
RS 485 Tx/Rx
–
2
NC
6
NC
3
NC
7
ECC22X2: 5 V
Other variants: reserved
4
RS 485 Tx/Rx+
8
ISO GND
If the RS-485 interface is located at the start or end of the bus topology:
Set switch S4 to ON
in order to switch on the 120 Ω terminal resistance between Tx/Rx+
and Tx/Rx
–.
As far as possible, the assignment of the interfaces should be carried out in accordance
with the specifications given in “MODBUS over Serial Line; Specification and
Implemen
tation Guide V1.02”.
Fig. 21: RS 485 switchable terminating resistor