Filling the circuit

FILLING THE CIRCUIT

Perform the following steps before starting up the system.

1 - FLUSHING AND SEAL TESTING THE SYSTEM

If copper piping has been used and joints have been hot 

brazed, flush out the system to remove any brazing resi-

dues. Seal test the system after you have flushed it out.

 

b

Fill the solar collector with glycol/water mix immedi-

ately after flushing it out, because flushing water may 

remain trapped in the circuit (with a consequent risk 

of freezing).

2 - PREMIXING WATER + GLYCOL

Glycol anti-freeze is supplied separately in standard vol-

umes and must be premixed with water in a suitable con-

tainer before being used to fill the system. For example, 

a mix of 40% glycol and 60% water provides anti-freeze 

protection down to a temperature of -21°C.

 

b

The propylene glycol supplied is specially formulat-

ed for solar collector applications and remains fully 

efficient throughout the -32 to +180°C temperature 

range. It is also non-toxic, biodegradable and bio-

compatible.

 

b

Do NOT part fill the circuit with pure glycol then add 

water later.

3 - FILLING

 

b

Only fill and bleed the solar circuit at ambient temper-
ature, with the collectors shielded from the sun’s rays.

1  Open the non-return valve (A)

2  Open the air vent at the highest point in the system (see 

figure alongside) and keep it open throughout the filling 

operation

3  Open the vent valve (7)

4  Pump the heat transfer fluid around the circuit with an 

external filling pump until all air bubbles have been 

eliminated. Close the manual bleed valve

5  Temporarily raise the pressure in the system to 4 bar

6  Start up the system for about 20 minutes

7  Bleed the circuit again from step 2 until all the air has 

been removed

8  Set the circuit pressure according to the table on the 

next page in order to ensure a minimum pressure of 1.5 

bar at the height of the collector field

9  Close the non-return valve (A) and any open vent valves 

to prevent the heat transfer fluid from evaporating.

 

b

Make sure that you have bled all the air out of the sys-

tem, using the water control system vent too.

Heat transfer fluid filling pump (accessory). A manual 

bleed valve is not required if this pump is used.

Anti-freeze

Temperature

Density

50%

-32 °C

1,045 kg/dm

3

40%

-21 °C

1,037 kg/dm

3

30%

-13 °C

1,029 kg/dm

3

A

R

M

7

Anti-freeze mix

Water control system

Heat

transfer fluid

filling pump

Solar collector

Manual

bleed valve

(accessory)

Heat exchanger

of solar

°C

M

T

Summary of Contents for 20095379

Page 1: ...SCF 20B Solar Solar Collector EN Installation manual Installation manual...

Page 2: ...mals caused by improper installation adjustment maintenance or use Range MODEL CODE SCF 20B 20095379 SCF 20B Pack of 2 20095380 SCF 20B Pack of 7 20095381 RANGE Contents CONTENTS The following symbols...

Page 3: ...011 7S2400F 13000000 BAR CODE 128B Anno di produzione SERIALE PROGRESSIVO Code Year of production Serial Number Description Flat plate solar collector Dimensions Gross area Aperture area Absorber area...

Page 4: ...scription U M IAM 50 0 87 Efficiency col 58 Tested according to EN 12975 referred to a 33 3 water glycol mix flow rate of 140 l h and irradiation G 800W m2 Tm Coll _inlet _temp Coll _outlet_temp 2 T m...

Page 5: ...e heat exchanger must be the one near the sensor pocket of the last collector of the line The connection with the circuit that comes back from the heat exchanger must be at the bottom of the first col...

Page 6: ...4 4 8 11 10 12 7 5 20 M 9 C 6 T M 2 Solar Regolator 17 15 16 18 3 R 1 1 19 19 Water control system 13 14 b b If copper pipes are used joints must be hot brazed b b We recommend the use of stainless st...

Page 7: ...em into service im mediately A B 1 1 Handling HANDLING Remove the PVC wrapping to free the solar collector from the pallet Apply the data label provided in the document enve lope to the back of the so...

Page 8: ...cted against damage by the weather and birds and animals Angle of collectors General Solar collectors are designed to be installed at angles of between 15 minimum and 75 maximum Make sure that the ble...

Page 9: ...lar circuit at ambient temper ature with the collectors shielded from the sun s rays 1 Open the non return valve A 2 Open the air vent at the highest point in the system see figure alongside and keep...

Page 10: ...ery two years MAINTENANCE Collector circuit Cold circuit pressure ____bar see table above Collector circuit seal test Safety valve check Anti freeze checked to ___ C pH of heat transfer fluid ____ Col...

Page 11: ...11...

Page 12: ...oilers com Beretta reserves the right to modify the characteristics and specifications given in this publication at any time and without prior notice as part of its policy of continuous product improv...

Reviews: