Installation
6005770_a – 07.04.2021
3.5.6
Connect the device from inside – BMK-L variant
The sensor tube must lead back to inside the kitchen. In order
to guarantee that the sensor tube works without faults:
y
The open end must lead directly into the kitchen’s air
space.
y
The sensor tube must not be kinked.
y
The measuring tube must not be closed or blocked.
The sensor tube must be extended if the space conditions
require it (maximum length 6 m).
D
Ø 14
☞
Drill an outlet for the connection cable from the wall
power supply in the exhaust air duct.
☞
Also drill an outlet for the sensor tube in the exhaust air
duct.
☞
Feed the cable through a grommet and the relevant
outlet in the exhaust air duct to the device.
To ensure that dismounting the drive unit is possible:
☞
Lay the connection cable and the sensor tube so that
there is a loop of approx. 250 mm in the exhaust air duct.
☞
Seal the outlets with the grommet.
☞
Connect the connection cable from the wall power
supply and the sensor tube to the device.
☞
Connect the exhaust air duct to the device’s inside wall.
☞
Plug the wall power supply’s plug into the socket.
The device is ready for operation.
3.5.7
Check and carry out commissioning
☞
Check that the mains cable and the electrical connection
cable are not kinked, crushed or damaged.
☞
Make sure that the protective film is removed.
☞
Check the correct functioning of the device.
D
The wall box opens when the cooker hood is operated. Once
the cooker hood is switched off, the wall box closes after a
short delay.