9
Installation
6005735_0 – 31.03.2021
EN
3.
Installation
3.1
Safety instructions for installation
D
WARNING!
Hazard through disregard of the installation instructions!
This chapter contains important information for the safe
installation of the device.
☞
Read through this chapter carefully before installing the
device.
☞
Follow the safety instructions.
☞
Carry out the installation as described.
y
Installation only by qualified specialist personnel.
D
“1.2 Authorised target groups” (page 4).
y
Electrical work must only be undertaken by qualified
electricians.
D
“1.2 Authorised target groups” (page 4).
y
Installation requires two persons.
y
When working at heights, ensure good stable footing
(e.g. stable stepladder).
y
The hob and other parts that can be touched must be
allowed to cool prior to installation.
y
Store the film or other parts of the packaging in a location
which is inaccessible to children.
y
The device must be in an undamaged and fault-free
condition prior to installation.
y
Cables must not be kinked, crushed or damaged.
y
Never open the fan housing.
y
It is not permissible to attach further components
(e.g. panels, air ducts) to the device.
y
The power supply voltage must match the voltage
information quoted on the ratings plate.
D
“2.5 Technical data” (page 8).
y
Ensure that the power supply is stable and remains so
prior to the installation.
Connect the power supply only when instructed to do so
in the installation instructions.
3.2
Requirements for the installation location
D
WARNING!
Risk of death due to improper installation!
Disregard of the ambient conditions can lead to hazardous
situations, e.g. in the handling of electrical power or gas.
☞
Make sure that the requirements for the installation
location are complied with.
y
Do not install in potentially explosive atmospheres.
y
With simultaneous use of a heating point which uses air
from the room as its oxygen supply (e.g. chimneys):
y
A safety device is absolutely essential.
y
The safety device must prevent gases being drawing
to the room.
y
It is essential to ensure that the negative pressure in
the heating point installation room does not exceed
4 Pa.
y
An approval for commissioning (e.g. from a chimney
sweep) must be available.
y
Installation is only permitted on structural building
elements capable of bearing the load (solid structure).
y
The ceiling must be level and horizontal.
y
If it is necessary to break through the wall:
A wall break-through influences the structural integrity
of the building. This work must only be carried out by a
specialist.
y
If installed above fireplaces that use solid fuels (e.g. coal
stove):
The fireplace must have a sealed cover which cannot be
removed. Otherwise there is a fire risk due to flying sparks.
Applicable legal and country-specific regulations must be
observed.
y
The air flowing out must be able to dissipate unimpeded.
Do not impede the air flow, e.g. through the installation of
objects on or at the device.
y
Make sure that the building electrical supply is properly
earthed.
y
The power supply voltage present must match the
voltage information quoted on the ratings plate.
y
For the supply of power, the customer must provide an
approx. 80 cm long connection cable in the vicinity of the
hood installation.
y
The mains plug must be accessible after the installation
of the hood. Alternatively, all-pole isolating device (with a
contact gap of at least 3 mm) must be provided.
Country-specific, legal provisions must be observed.
Summary of Contents for BIH 100 GL
Page 36: ...6005735_0 31 03 2021 ...