Re cor ding/Play back of Vo i ce Mes sa ges
The re cor ding/ play back of Vo i ce Mes sa ges is ob ta i ned from the con trol pa nel front
pla te, as de scri bed be low.
+
To im pro ve the qua lity of the re cor ding, open the co ver of the con trol unit be fo re
re cor ding vo i ce mes sa ges.
From the main scre en:
F1=Pro gram
l1-stat:ACTIVE
F2=Chan ge
Ma ster Con trol pa nel
F3=Anal yze
IS SCANNING LOOPs
F4=More 11:20:25 - 02/08/2008
1. Press F1 (Pro gram) :
Ma ster Con trol pa nel l1-stat:PROGRAM
INSTALLER
Insert Pa
ssword
[_____]
2. Di git Ize the Pa ssword Instal ler (fac tory set ting: 00000) and press GO:
Ma ster Con trol pa nel l3-stat:PROGRAM
1=Auto 2=Disp 3= SW Zo
nes 4=Out
puts
5=Net work 6=Comm.7=Options 8=System
9=Default 0=PWD L3
3. Press key 6 (Com mu nic.) :
Ma ster Con trol pa nel l3-stat:PROGRAM
PSTN i/f :
Up or down to se
lect Type
4. Press
Ý
or
Þ
to view PSTN i/f, so press GO:
Ma ster Con trol pa nel l3-stat:PROGRAM
F2=REC
MESSAGE [01]
F3=PLAY
F4=STOP STOP He a der Mes sa ge
Ø
MESSAGE [01]
- shows the Vo i ce Mes sa ge num ber
which will be re cor ded/ pla yed back;
Ø
STOP
- shows Vo i ce Mes sa ge sta tus;
Ø
He a der Mes sa ge
- shows the De scrip tion as si gned to the Vo i ce Mes sa -
ge.
5. Press
Û
or
Ü
to view the Mes sa ge which you want re cord/ play back:
Ma ster Con trol pa nel l3-stat:PROGRAM
F2=REC
MESSAGE [02]
F3=PLAY
F4=STOP
STOP
Alarm Mes sa ge
6. Press F2 (REC) to start re cor ding the Mes sa ge, press F3 (PLAY) to start the Mes -
sa ge play back or press ESC to se lect anot her Mes sa ge (step no. 5) :
Ma ster Con trol pa nel l3-stat:PROGRAM
F2=REC
MESSAGE [02]
F3=PLAY
F4=STOP
REC
Alarm Mes sa ge
Ø
- shows the re cor ding/ play back time (ver ti cal da shes) with re gard to the ava i la -
ble time (ho ri zon tal da shes): each ho ri zon tal dash re pre sents 1 se cond;
Ø
REC - in di ca tes that the Vo i ce Mes sa ge is be ing re cor ded;
Ø
PLAY - in di ca tes that the Vo i ce Mes sa ge is be ing pla yed back.
7. To re cord the Mes sa ge, spe ak into the mi crop ho ne which is po si tio ned on the
front pla te of the con trol pa nel (MIC), from a di stan ce of abo ut 20 cm, with nor mal
tone and pitch.
8. Press F4 (STOP) to stop the re cor ding/ play back of the Mes sa ge and go back to
step no. 6.
Description of ter mi nals
1-2 [L.E.]
Exter nal te lep ho ne line
3-4 [L.I.]
Inter nal te lep ho ne line
5 [
-
]
Earth
Tec ni chal Spe ci fi ca tions
No mi nal Vol ta ge
27,6 V
Min. Voltage
19,0 V
Max Voltage
27,6 V
Ma xi mum dra in
200 mA
Stand-by dra in
50 mA
Wor king tem pe ra tu re
-5 ÷ +40 °C
Dimensionis(L*H)
103,5*113,35 mm
Note: observance of Standards
The stan dard EN 50136-1-1 (Ge ne ral re qui re ments for alarm tran smis sion systems)
re qui res the tran smis sion system (FC500PSTN P.C.B., tran smis sion net work and
re ce i ver) to ob ser ve spe ci fic va lu es in terms of ava i la bi lity (the per cen ta ge of time
du ring which the system may be used to tran smit in for ma tion to the mo ni to ring cen -
tre). The fol lo wing ta ble is sup plied for the cal cu la tion of the ma xi mum an nual tran -
smis sion net work and re ce i ver una va i la bi lity; it lists the una va i la bi lity (the 100
com ple ment of ava i la bi lity) of the FC500PSTN P.C.B. and the re si dual una va i la bi -
lity (the 0.2% com ple ment of the FC500PSTN una va i la bi lity) of the tran smis sion net -
work and re ce i ver, ba sed on the re pa ir time gua ran te ed for that par ti cu lar P.C.B.
Re pa ir time
(days)
Ava i la bi lity
(%)
Una va i la bi lity
(%)
Re si dual
Una va i la bi lity
(%)
1
99,989583875840
0,0104
0,1896
2
99,979169921366
0,0208
0,1792
3
99,968758135902
0,0312
0,1688
4
99,958348518769
0,0417
0,1583
5
99,947941069290
0,0521
0,1479
6
99,937535786789
0,0625
0,1375
7
99,927132670588
0,0729
0,1271
8
99,916731720010
0,0833
0,1167
9
99,906332934381
0,0937
0,1063
10
99,895936313024
0,1041
0,0959
11
99,885541855263
0,1145
0,0855
12
99,875149560422
0,1249
0,0751
13
99,864759427828
0,1352
0,0648
14
99,854371456806
0,1456
0,0544
15
99,843985646680
0,1560
0,0440
16
99,833601996776
0,1664
0,0336
17
99,823220506421
0,1768
0,0232
18
99,812841174942
0,1872
0,0128
19
99,802464001664
0,1975
0,0025
20
99,792088985914
0,2079
-0,0079
For exam ple: if the re pa ir time is one day, the tran smis sion net work and the re ce i ver
can not have – in one year – an una va i la bi lity va lue (cal cu la ted as in di ca ted in stan -
dard EN 50136-1-1) gre a ter than 0.1896%.
We can see from the ta ble that, if the re pa ir time is equal to or gre a ter than 20 days, it
will not be pos si ble to meet the re qui re ments of the stan dard, even if the tran smis -
sion net work and re ce i ver fun ction per fectly (i.e. they are al ways ava i la ble).
Fur ther mo re, still in ac cor dan ce with EN 50136-1-1, the tran smis sion time must be
gua ran te ed as be ing shor ter than 60 se conds.
The re ce i ver for the sur ve il lan ce con trol unit must be pro gram med in com plian ce
with this re qui re ment.