600V/1000V DC Combiner Installation and Operating Instructions – 36-String Disconnect Models
950-002305-000 Rev A
19
Chapter 3: Installation Procedure
Preparing to Install the Disconnect Combiner
Refer to the project drawings to identify the mounting location and any specific
location requirements or special instructions.
The mounting area must be at least as large as the enclosure to be mounted and
be able to support the weight of the equipment.
When wall or roof mounting the enclosure, it must be secured to a rigid
substrate, using appropriately sized hardware.
When mounting the enclosure horizontally, it is recommended that it be
mounted at an angle of at least 15 degrees to prevent water pooling on the
door.
The enclosure can be mounted vertically or at any angle in between fully
vertical (90 degrees) and horizontal.
When installing in climates with snowfall, the combiner must be mounted
vertically.
It is not recommended that it be mounted in any position such that the door
drops down when opened.