Learning Basic Features
79
Lea
rni
890054-00-00
GM2 Series VFD
Auto Torque Boost
In V/F operation, auto torque boost adjusts the output voltage when the motor cannot be started
due to lack of starting torque. It provides a calculated voltage boost based on torque current.
Group Code
Name
Setting
Setting Range
Unit
dr
15
Torque boost
mode
1 Auto
0
–
1
-
dr
26
Auto torque
boost filter gain
2
1
–
1000
-
dr
27
Auto torque
boost motoring
voltage gain
50.0
0.0
–
300.0
%
dr
28
Auto torque
boost
regeneration
voltage gain
50.0
0.0
–
300.0
%
Set dr.15 (Torque Boost mode) to 1 (auto). Parameters dr.26, dr.27, and dr.28 can be adjusted when
there is a lack of starting torque or when excessive current is flowing. This method outputs voltage
by adding a voltage boost quantity calculated using torque current values from the manual torque
boost settings (dr.16, dr.17).
Auto Torque Boost does not require Auto-Tuning but does require
motor’s
nameplate ratings
entered in the following parameters:
Code
Name
Setting Range
dr.18
Base frequency
30.00
–400.00 (Hz)
bA.12
Rated slip speed
0
–3000 (Rpm)
bA.13
Motor rated current
1.0
–1000.0 (A)
bA.14
Motor noload current
0.0
–1000.0 (A)
If you do not use motor’s
nameplate ratings, each parameter is set to a default value and the auto
boost function may not be as effective.
Summary of Contents for RSi GM2 Series
Page 2: ...ii...
Page 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Page 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Page 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Page 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...