GM2 Series VFD
890054-00-00
Learning Basic Features
Command Source (Start/Stop) Configuration
The GM2 inverter provides several methods to Start and Stop the inverter. Choices include the
keypad, digital input terminals, RS-485 (Modbus), or Fieldbus option cards.
Group
Code
Name
Setting
Setting Range
Unit
Operation drv
Command
Source
0
Keypad
0
–
4
-
1
Fx/Rx-1
2
Fx/Rx-2
3
Int 485
4
Fieldbus
Setting the Keypad as a Command Input Device
The keypad can be selected as a command input device to start and stop the inverter. Set
parameter drv (command source) to 0 (Keypad). Press the [RUN] key on the keypad to start and the
[STOP/RESET] key to stop.
Group
Code
Name
Setting
Setting Range
Unit
Operation drv
Command
Source
0
Keypad
0
–
4
-
Setting the Terminal Block as a Command Input Device -
Fwd/Rev Run Commands
Digital input terminals can be selected as the command input device. Set parameter drv (command
source) to 1 (Fx/Rx-1). Choose (2) of the digital input terminals (P1 ~ P5) to setup as Forward and
Reverse. Set (2) of the correspondinig parameters (In.65~In.69) to 1 (Fx) and 2 (Rx) respectively.
Activating either terminal constitutes a run command. Activating both terminals constitutes a stop
command.
Group
Code
Name
Setting
Setting Range
Unit
Operation drv Command Source 1
Fx/Rx-1
0
–
4
-
In
65
–
69
Px terminal
setting options
1
Fx
0
–
52
-
2
Rx
Fwd/Rev Command using Digital Input Terminals
–
Setting Details
Code and
Features
Description
Operation group
drv
–
Cmd Source
Set to 1 (Fx/Rx-1).
In.65
–
69 Px
Define
Assign a terminal for forward (Fx) operation.
Assign a terminal for reverse (Rx) operation.
Summary of Contents for RSi GM2 Series
Page 2: ...ii...
Page 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Page 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Page 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Page 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...