Learning Protection Features
162
GM2 Series VFD
890054-00-00
Inverter and Sequence Protection
Input/Output open-phase protection
Open-phase monitoring and protection can be set to either or both the input and output of the
inverter. The protection is used to prevent overcurrent levels at the inverter input and/or output
due to an open-phase. An open-phase at output may cause the motor to stall due to a lack of
torque. For input phase open, a voltage level can be set (Pr.06), below which the inverter will trip.
Group Code
Name
Setting
Setting Range
Unit
Pr
05
Input/output open-
phase protection
00*
-
bit
06
Input voltage range
during open-phase
15
1
–
100 V
V
*Displayed as
on the Keypad.
Input and Output Open-phase Protection Setting Details
Code and
Features
Description
Pr.05 Phase Loss
Chk,
Pr.06 IPO V Band
Input and/or output phase protection can be selected. When the top
LED segment is on, the corresponding bit is set On (1). When the
bottom LED segment is on, the corresponding bit is Off (0). Bit 0 is for
output phase monitoring, Bit 1 is for input phase monitoring.
Items
Bit On Status
Bit Off Status
Keypad
Configuration
Function
Bit1
Bit0
✓
Output open-phase protection
✓
Input open-phase protection
Initial values off input voltage range during open-phase are shown as
below.
Items
Initial Value
Unit
1.0 HP ~ 5.0 HP (0.4 kW~4.0 kW)
(240 V/480 V)
15
V
7.5 HP ~ 15 HP (5.5 kW~11 kW)
(240 V/480 V)
13
V
Summary of Contents for RSi GM2 Series
Page 2: ...ii...
Page 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Page 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Page 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Page 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...