61
6
Function
Code
Name
Setting Range
Default
Change
Group F0: Standard Parameters (continued)
F0-27
Running c
frequency source
Units position: operating panel (keypad and
display) + frequency reference
setting channel
0: No function
1: Digital setting
2: AI1
3: AI2
4: AI3
5: Pulse reference (DI5)
6: Multi-reference
7: Simple PLC
8: PID reference
9: Serial communication
Tens position: terminal I/O c frequency
reference setting channel
Hundreds position: serial communication
+ frequency reference
setting channel
0000
✩
F0-28
Serial port communication
protocol
0: Modbus protocol
1: PROFIBUS-DP or CANopen protocol
0
★
Group F1: Motor 1 Parameters
F1-00
Motor type selection
0: Common asynchronous motor
1: Variable frequency asynchronous motor
0
★
F1-01
Rated motor power
0.1 to 1000.0 kW
Model
dependent
★
F1-02
Rated motor voltage
1 to 2000 V
Model
dependent
★
F1-03
Rated motor current
0.01 to 655.35 A (AC drive power ≤ 55 kW)
0.1 to 6553.5 A (AC drive power > 55 kW)
Model
dependent
★
F1-04
Rated motor frequency
0.01 Hz to max. frequency
Model
dependent
★
F1-05
Rated motor speed
1 to 65535 RPM
Model
dependent
★
F1-06
Stator resistance
0.001 to 65.535 Ω (AC drive power ≤ 55 kW)
0.0001 to 6.5535 Ω (AC drive power > 55 kW)
Auto-tuning
parameter
★
F1-07
Rotor resistance
0.001 to 65.535 Ω (AC drive power ≤ 55 kW)
0.0001 to 6.5535 Ω (AC drive power > 55 kW)
Auto-tuning
parameter
★
F1-08
Leakage inductive
reactance
0.01 to 655.35 mH (AC drive power ≤ 55 kW)
0.001 to 65.535 mH (AC drive power > 55 kW)
Auto-tuning
parameter
★
F1-09
Mutual inductive
reactance
0.1 to 6553.5 mH (AC drive power ≤ 55 kW)
0.01 to 655.35 mH (AC drive power > 55 kW)
Auto-tuning
parameter
★
F1-10
No-load current
0.01 to F1-03 (AC drive power ≤ 55 kW)
0.1 to F1-03 (AC drive power > 55 kW)
Auto-tuning
parameter
★
F1-37
Auto-tuning selection
0: No auto-tuning
1: Asynchronous motor partial static auto-tuning
2: Asynchronous motor dynamic auto-tuning
3: Asynchronous motor complete static auto-
tuning
0
★