background image

Operating manual 

DUSPOL

®

 combi

Before  using  the  voltage  tester  DUSPOL

®

  combi: 

Please  read  the  operating  manual  carefully  and 

always observe the safety instructions! 

List of contents:

1.  Safety instructions 

2.   Functional description of the voltage tester

3.   Functional test of the voltage tester 

4.   How to test AC voltages

4.1   How to test the phase at AC voltage

5.   How to test DC voltages

5.1  How to test the polarity at DC voltage 

6.   How  to  test  an  electrically  conductive 

connection (continuity check) 

6.1   How to test the conducting and non-conducting 

direction of semiconductors

7.   General maintenance

8.   Technical data

1.  Safety instructions:

-   Hold  the  voltage  tester  only  by  the  insulated 

handles   and   and do not touch the contact 

electrodes (probe tips) 

-   Immediately  before  use:  Check  the  voltage 

tester for correct operation! (see chapter 3). The 

voltage tester must not be used if one or several 

display functions fail or if the voltage tester is not 

ready to operate (IEC 61243-3)! 

-   The voltage tester (voltage class A) must be used 

only within the nominal voltage range of 12 V up 

to AC 400 V/ DC 750 V!

-   The voltage tester complies with protection class 

IP 64 and therefore can also be used under wet 

conditions (designed for outdoor use). 

-   For testing, firmly grasp the voltage tester by the 

handles   and  . 

-   Never  connect  the  voltage  tester  to  voltage  for 

longer  than  30  seconds  (maximum  permissible 

operating time = 30 s)! 

-   The  voltage  tester  only  operates  correctly 

within  the  temperature  range  of  -10 °C  up  to

+55 °C  at  relative  air  humidity  of  20 %  up  to 

96 %. 

-   Do not dismantle the voltage tester!

-   Please protect the housing of the voltage tester 

against contamination and damages! 

-   Please  store  the  voltage  tester  under  dry 

conditions.

-   To prevent injuries and discharge of the battery, 

provide  the  contact  electrodes  (probe  tips) 

with  the  enclosed  cover  after  using  the  voltage 

tester! 

Attention: 

After maximum load (i.e. after a measurement of 30 

seconds at AC 400 V/ DC 750 V), the voltage tester 

must not be used for a duration of 240 seconds!

The  voltage  tester  is  marked  with  international 

electric  symbols  and  symbols  for  indication  and 

operation with the following meaning:

symbol

meaning
Device or equipment for working under 

voltage 

Push button

Alternating current (AC)

Direct current (DC)

Direct  and  alternating  current  (DC 

and AC)

Push  button  (manually  actuated); 

indicates  that  respective  indications 

only  occur  when  both  push  buttons 

are actuated

Symbol for phase and continuity test

2.  Functional description 

The  DUSPOL

®

  combi  is  a  two-pole  voltage  tester 

according  to  IEC  61243-3  with  visual  display.  As  a 

supplementary device, the voltage tester is equipped 

with  a  continuity  check  function.  For  this  function, 

the  voltage  tester  has  two  built-in  solar  cells.  The 

signaling  of  the  continuity  check  is  done  optically 

by  means  of  a  LC  display.  The  voltage  tester  is 

designed  for  DC  and  AC  voltage  tests  within  the 

voltage  range  of  12  V  up  to  AC  400  V/DC  750  V. 

It  can  be  used  to  perform  polarity  tests  in  DC  and 

phase tests in AC. The voltage tester consists of the 

test probes L1   and L2   and a connecting cable 

.  The  test  probe  L1   is equipped with a display 

. Both test probes are provided with  push buttons 

. Without pressing both push buttons, the following 

voltage  steps  (AC  or  DC)  can  be  indicated:  24 V+; 

24 V-; 50 V; 120 V; 230 V; 400 V; 750 V. By pressing 

both  push  buttons,  the  voltage  tester  switches  to  a 

lower  internal  resistance  (suppression  of  inductive 

and  capacitive  voltages).  Thus,  also  the  indication 

of  12 V+  and  12 V–  is  activated.  Furthermore,  a 

vibrating motor (motor with a flyweight) is put under 

voltage. From approximately 200 V this motor is set 

in rotation. With the voltage increasing, the motor’s 

speed  and  vibration  increases  as  well  so  that 

additionally by means of the handle of test probe L2 

 the voltage value can be estimated roughly (e.g. 

230/  400 V).  The  duration  of  the  test  with  a  lower 

internal resistance of the device (load test) depends 

on  the  value  of  the  voltage  to  be  measured.  To 

prevent excessive warming of the voltage tester, it is 

equipped with a thermal protection (reverse control). 

With this reverse control, the speed of the vibrating 

motor decreases as well. 

Display field

The  display  system  consists  of  high-contrast  light-

emitting diodes (LED) 

 indicating DC and AC voltages 

in steps of 12 V; 24 V; 50 V; 120 V; 230 V; 400 V; 750 V 

. The indicated voltages are nominal voltages. With 

DC voltage, the LEDs also indicate the polarity for 12 V 

and 24 V (see chapter 5). The 12 V LED can only be 

activated by pressing both push buttons.

The  two  solar  cells  are  top  left  and  bottom  right  of 

the  display  field.  These  cells  generate  the  auxiliary 

voltage necessary for the continuity check.

LC display

The  LC  display 

  serves  for  the  phase  test  with 

alternating current (AC) and indicates the successful 

continuity check.

3.  Functional check 

-   The  voltage  tester  must  be  used  only  within 

the  nominal  voltage  range  of  12 V  up  to 

AC 400 V/ DC 750 V!

-   Never  connect  the  voltage  tester  to  voltage  for 

longer  than  30  seconds  (maximum  permissible 

operating time = 30 s)!

-   Check  the  voltage  tester  for  correct  function 

immediately before use! 

-   Test  all  functions  by  means  of  known  voltage 

sources. 

 

•   For DC voltage tests use e.g. a car battery. 

 

•   For  AC  voltage  tests  use  e.g.  a  230 V 

socket.

 

•   Connect the two test electrodes 

 to test the 

continuity check function.

Do not use the voltage tester unless all functions are 

operating correctly!

Check the function of the LC display 

 by single-pole 

connection of the contact electrode of the test probe 

L1   to an external conductor (phase).

4.  How to test AC voltages 

-   The voltage tester must be used only within the 

nominal voltage range of 12 V up to AC 400 V!

-   Never  connect  the  voltage  tester  to  voltage  for 

longer  than  30  seconds  (maximum  permissible 

operating time = 30 s)!

-   Firmly grasp the insulated handles   and   of 

the test probes L1 and L2.

-   Place the contact electrodes 

 of the test probes 

L1   and L2   against the relevant points of the 

unit under test. 

-   For  AC  voltages  from  24 V  onwards  and  when 

pressing both push buttons (load test) from 12 V 

onwards, the LEDs “plus” and “minus” 

 and 

 

light up. Furthermore, all LEDs light until the step 

value of the applied voltage is reached. 

-   When  pressing  both  push  buttons 

  and  from 

an applied voltage of approx. 200

 

V onwards, a 

vibrating  motor  is  put  in  rotation  inside  the  test 

probe  L2  .  With  the  voltage  increasing,  the 

speed of this motor is increasing as well.

Please make sure that you touch the voltage tester at 

the insulated handles of test probes L1   and L2   

only! Do not cover the display and do not touch the 

contact electrodes!

4.1  How to test the phase at AC voltage 

-   The voltage tester must be used only within the 

nominal voltage range of 12 V up to AC 400 V! 

-   The phase test is possible in the earthed mains 

from 230 V onwards! 

-   Firmly grasp the handle of test probe L1  . 

-   Place the contact electrode 

 

of test probe L1   

against the relevant point of the unit under test.

-   Never  connect  the  voltage  tester  to  voltage  for 

longer  than  30  seconds  (maximum  permissible 

operating time = 30 s)!

Never  touch  the  contact  electrode  of  test  probe  L2 

during the single-pole test (phase test)!

If  the  symbol  ” ”  appears  on  the  LC  display 

,  the 

phase of an alternating voltage (AC) is at this point of 

the unit under test. 

Note: 

The reading of the LC display 

 might be impaired 

due  to  unfavorable  light  conditions,  protective 

clothing or in insulated locations.

5.  How to test DC voltages 

-   The voltage tester must be used only within the 

nominal voltage range of 12 V up to DC 750 V!

-   Never  connect  the  voltage  tester  to  voltage  for 

longer  than  30  seconds  (maximum  permissible 

operating time = 30 s)!

-   Firmly grasp the insulated handles   and   of 

the test probes L1 and L2.

-   Place the contact electrodes 

 of the test probes 

L1   and L2   against the relevant points of the 

unit under test. 

-   For  AC  voltages  from  24 V  onwards  and  when 

pressing both push buttons (load test) from 12 V 

onwards, the LEDs “plus” and “minus” 

 and 

 

light up. Furthermore, all LEDs light until the step 

value of the applied voltage is reached. 

-   When  pressing  both  push  buttons 

  and  from 

an applied voltage of approx. 200 V onwards, a 

vibrating  motor  is  put  in  rotation  inside  the  test 

probe  L2  .  With  the  voltage  increasing,  the 

speed of this motor is increasing as well.

Please make sure that you touch the voltage tester at 

the insulated handles of test probes L1 and L2 only! 

Do not cover the display and do not touch the contact 

electrodes!

5.1  How to test the polarity at DC voltage 

-   The voltage tester must be used only within the 

nominal voltage range of 12 V up to DC 750 V!

-   Never  connect  the  voltage  tester  to  voltage  for 

longer  than  30  seconds  (maximum  permissible 

operating time = 30 s)!

-   Firmly grasp the insulated handles   and   of 

the test probes L1 and L2.

-   Place the contact electrodes 

 of the test probes 

L1   and L2   against the relevant points of the 

unit under test. 

-   If LED 

 lights up, the “positive pole” of the unit 

under test is at test probe  .

-   If LED 

 lights up, the “negative pole” of the unit 

under test is at test probe  .

Please make sure that you touch the voltage tester at 

the insulated handles of test probes L1   and L2    

only! Do not cover the display and do not touch the 

contact electrodes!

6.   How  to  test  an  electrically  conductive 

connection (continuity check) 

-   The  continuity  check  must  be  performed  on 

the relevant points of a “dead” (not being under 

voltage)  unit  under  test.  If  necessary,  the 

capacitors must be discharged. 

-   The necessary test voltage is supplied by means 

of the power supply (2 solar cells) integrated in 

the test probe L1  .

-   The  test  is  possible  within  the  range  of 

0 - 600 kΩ. 

-  Firmly grasp the handles   and  . 

-   Place the test probes   and   with the contact 

electrodes 

  against  the  relevant  points  of  the 

unit under test. 

-   When  contacting  an  electrically  conductive 

connection    with  the  contact  electrodes 

,  the 

symbol ” ”  appears on the LC display 

Note:

When  actuating  both  push  buttons,  the  system 

measures its own internal resistance!

6.1   How  to  test  the  conducting  and  non-

conducting direction of semiconductors 

-   The polarity-depending test must be performed 

on  the  relevant  points  of  a  “dead”  (not  being 

under voltage) unit under test. 

-   The necessary test voltage is supplied by means of 

the power supply (2 solar cells) integrated in the test 

probe  . Test probe L1   is  the “positive pole”. 

-   The test is possible within the range of 0 - 600 kΩ 

or 1 P-N junction (diode). 

-   Firmly grasp the handles   and   . 

-   Place the contact electrodes 

 of the test probes 

 and   against the relevant points of the unit 

under test.

-   In case of current flow of the measuring voltage 

in  conducting  direction  to  a  semiconductor,  the 

symbol ” ” appears on the LC display 

. In case 

of  contacting  in  non-conducting  direction,  no 

indication must appear. 

Note:

When  actuating  both  push  buttons,  the  system 

measures its own internal resistance!

7.   General maintenance

Clean  the  exterior  of  the  housing  with  a  clean  dry 

cloth  (exception:  special  cleansing  cloths).  Do  not 

use solvents and/ or abrasives to clean the voltage 

tester.

8.  Technical data: 

-   Guideline for two-pole voltage testers:  

IEC 61243-3 

-  Protection class: IP 64, IEC 60529 

 

(DIN 40050), also for outdoor use!

-  Nominal voltage range (voltage class A): 

 

12 V to AC 400 V/ DC 750 V 

-  Internal resistance, measuring circuit: 

 

180 kΩ, parallel 4.7 nF (2.35 nF)

-   Internal  resistance,  load  circuit  –  both  push 

buttons actuated!: approx. 3.7 kΩ...(150 kΩ)

-   Current  consumption,  measuring  circuit: 

max. I

n

 3.3 mA (400 V ) AC/ 4.4 mA (750 V) DC

-   Current  consumption,  load  circuit  –  both  push 

buttons actuated!: I

0.2 A (750 V)

-   Polarity indication: LED +; LED - 

 

(indicating handle = positive polarity)

-   Indicating steps LED: 12 V+*, 12 V-*, 24 V+, 24 V-, 

50 V,  120 V,  230 V,  400 V  and  750 V  (*:  only  with 

both push buttons actuated)

-   max. indicating errors: U

n

 ± 15 %, ELV U

n

 – 15%

-  Nominal frequency range f: 0 to 60 Hz 

-  Phase indication: ≥ U

n

 

230 V

-  Vibrating motor, starting: ≥ U

n

 230 V

-   max. permissible operating time: ED = 30 s (max. 

30 seconds) , 240 s pause

-  Test current, continuity check: max. 5 μA

-  Idling voltage, continuity check: max. 5 V

-  Testing range, conducting resistance: 

 

0 - 600 kΩ, 1 P-N junction (diode)

-  Solar cells: 2 x 1.75 cm²

-  Weight: approx. 170 g

-  Connecting cable length: approx. 900 mm

-   Operating and storing temperature range: -10 °C 

to +55 °C  (climate category N)

-   Relative  air  humidity:  20 %  to  96 %  (climate 

category N)

-  Reverse control times (thermal protection):

voltage

time

230 V

30 s

400 V

9 s

750 V

2 s

D

U

S

P

O

L

®

 

combi

BENNING Elektrotechnik & Elektronik GmbH & Co.KG

Münsterstraße 135 - 137 • D - 46397 Bocholt

T+49 (0) 2871 - 93 - 0 • Fax ++49 (0) 2871 - 93 - 429

www.benning.de • E-Mail: [email protected]

 Bedienungsanleitung

 Operating manual

 Mode d‘emploi

 

Manuel de instrucciones

  Инструкция за експлоатация

CZ

  Návod k použití zkoušečky

 

Brugsanvisning

FIN

  Käyttöohje

 Οδηγίες χρήσεως

 Használati utasítás

 Istruzioni per l’uso

LT 

Naudojimosi instrukcija

 Bruksanvisning

 Gebruiksaanwijzing

 Instrukcja obsługi

RUS

   Инструкция по эксплуатации 

индикатора напряжения

 Bruksanvisning

 

T.-Nr

. 756154.01/ 1

1-2003

geprüft und zugelassen

Reviews: