BENNING IT 115
Device description
- 20 -
A high interference voltage has been detected during measurement. This
might result in incorrect measuring results.
L and N have been interchanged.
RCD has been tripped during measurement (in RCD functions).
Portable RCD (PRCD) has been selected (only for documentation purposes).
The test cable resistance for low-impedance measurement / continuity test
has not been compensated.
The test cable resistance for low-impedance measurement / continuity test
has been compensated.
High earthing resistance of the measuring probes. This might result in
incorrect measuring results.
The measuring signal is outside the measuring range This might result in
incorrect measuring results.
Fuse F1, F2 or F3 is defective.
If one of the fuses F2 or F3 has blown, the device must not be used anymore.
In this case, the device must be sent to BENNING for inspection and repair.
4.1.4 Evaluation field
The measuring result is within the preset limiting values (green LED).
The measuring result is outside the preset limiting values (red LED).
Measurement has been aborted. Please observe the warnings and messages
displayed.
4.1.5 Acoustic warning signals
Continuous
sound
Warning!
Dangerous voltage at the PE connection!