Technical data
74
TM800_D00165_00_M_XXEN/06.2015
Operating and display modules and I/O modules
Operating and display modules BI800S:
Max. number of illuminated pushbuttons ...................................................................................................................... 80
Buttons/alarm LEDs per panel............................................................................................................................................5
Power consumption ................................................................................................................................................ ≤ 2 VA
I/O module:
Maximum number of inputs and outputs............................................................................................................. 192/192
Environment/EMC
EMC .................................................................................................................................................................. EN 61326-1
Ambient temperatures:
Operating temperature ................................................................................................................................. -5…+55 °C
Transport ..................................................................................................................................................... -25…+70 °C
Long-term storage ...................................................................................................................................... -25…+55 °C
Classification of climatic conditions acc. to IEC 60721:
Stationary use (IEC 60721-3-3) ................................................................... 3K5 (no condensation, no formation of ice)
Transport (IEC 60721-3-2) .......................................................................................................................................... 2K3
Long-term storage (IEC 60721-3-1) ........................................................................................................................... 1K4
Classification of mechanical conditions acc. to IEC 60721:
Stationary use (IEC 60721-3-3) .................................................................................................................................. 3M4
Transport (IEC 60721-3-2) ......................................................................................................................................... 2M2
Long-term storage (IEC 60721-3-1) .......................................................................................................................... 1M3
Option "W" data different from the standard version:
Classification of climatic conditions acc. to IEC 60721:
Stationary use (IEC 60721-3-3) ..................................................... 3K5 (condensation and formation of ice is possible)
Classification of mechanical conditions acc. to IEC 60721:
Stationary use (IEC 60721-3-3) .................................................................................................................................. 3M7
Connection properties (supply voltage, BMS bus):
Rigid/flexible/conductor sizes .......................................................................0.2…2.5/0.2…2.5 mm
2
/AWG 24…-12
Flexible with ferrules, without/with plastic sleeve ............................................................ 0.25…2.5/0.25…2.5 mm
2
Connection properties (inputs):
Rigid/flexible/conductor sizes ....................................................................... 0.08…1.5/0.08…1.5 mm
2
/AWG 28-16
Flexible with ferrules, without/with plastic sleeve .............................................................0.25…1.5/0.25…0.5 mm
2
Stripping length ..........................................................................................................................................................7 mm
Tightening torque ......................................................................................................................................... 0.5…0.6 Nm
Other
Operating mode .................................................................................................................................continuous operation
Mounting ...................................................................................................................................................display-oriented
Connection ...............................................................................................................................................plug-in terminals
Degree of protection, built-in components (DIN EN 60529) ...................................................................................... IP50
Degree of protection, terminals (DIN EN 60529) ........................................................................................................ IP20
Flammability class..................................................................................................................................................UL94V-0
Weight..........................................................................................................................according to the respective version
9.1.1
Standards, approvals and certifications
The TM800 remote alarm indicator and operator panels comply with the requirements of IEC 60364-
7-710, DIN VDE 0100-710.