Menu mode: Operation and setting
60
TM800_D00165_00_M_XXEN/06.2015
1. Exit
Back to the main menu
2. Edit table
Use the arrow buttons to select the line "No" and confirm with the "
↵
" button.
Use the arrow buttons to set the external BMS bus address "Ext" and confirm
with the "
↵
" button.
Use the arrow buttons to set the internal BMS bus address "Int" and confirm
with the "
↵
" button. Use the arrow buttons to select the external system
number "Syst." and confirm with the "
↵
" button.
TM800 always adds a new line at the end of the table. This line can be mod-
ified (e.g. 4 000 000 00 off). In this way, other alarm addresses can be activat-
ed.
3. Clear table
Deactivate all addresses ("off"). "Clear table" is only possible when no test
addresses are activated.
Possible settings for the system number "Syst.":
8.4.4.3
Settings menu 3: Test addresses
Set the bus addresses for insulation monitoring devices (z. B. 107TD47, IRDH…), transfer switching
devices with monitoring functions (ATICS®), LIM (Line Isolation Monitors) and GFCI (Ground Fault Cir-
cuit interrupters), which are required to carry out a test when the "TEST" button is pressed. The set-
ting can only be made for devices which have also been activated in the "Alarm addresses" menu
and/or programmed for individual alarm texts. Individual alarm texts are a minimum requirement
for:
Channel 1…3 (setting "107TD47")
Channel 1
(setting "IRDHxxx")
Syst. Meaning
00
There's no text in line 1 of the alarm message.
01…04
Texts of "System 01" to "System 04" are displayed.
T
Programmed text is displayed.
Off
Deletes the current line of the table
1.Exit
No Ext Int Syst.
1 000 003 01
---Alarm addresses---
1.Exit
2.Edit table
3.Clear table
Indiv. Assignm.: 4
1.Exit
2.Edit table
3.Clear table
1.Exit
No Ext Int Type
1 000 003 107TD
---Test addresses---