![Bender RCMA423AS Manual Download Page 24](http://html1.mh-extra.com/html/bender/rcma423as/rcma423as_manual_2731740024.webp)
Operation and setting
24
RCMA423AS_D00157_01_M_XXEN/08.2016
5.2
Function of the operating elements
Device front
Ele-
ment
Function
ON,
green
Lighting continuously: Power On
Flashing:
system fault or connection monito-
ring fault
AL1,
AL2
LED Alarm 1 lights (yellow):
Response value 1 reached
(
I
Δ
n1
)
LED Alarm 2 lights (yellow): Res-
ponse value 2 reached
(
I
Δ
n2
)
13 mA
M
13 mA flow through the measuring
current transformer,
fault memory active
T,
Test button (> 1.5 s):
to indicate the display elements in
use, to start a self test;
Up key (< 1.5 s):
Menu items/values
R,
Reset button (> 1.5 s):
Deleting the fault memory;
Down key (< 1.5 s):
Menu items/values
MENU,
MENU key (> 1.5 s):
Starting the menu mode;
Enter key (< 1.5 s):
Confirm menu item, submenu item
and value.
Enter key (> 1.5 s):
Back to the next higher menu level.
ON
AL1 AL2
T
MENU
R