Data
35
RCMA420_D00059_04_M_XXEN/05.2021
6.3
Technical data
( )* = factory setting
Insulation coordination acc. to IEC 60664-1/IEC 60664-3
Insulation coordination acc. to IEC 60664-1/IEC 60664-3
RCM420-D-1
Rated insulation voltage ........................................................................................................................... 100 V
Overvoltage category/ pollution degree ...................................................................................................... III/3
Rated impulse voltage ..............................................................................................................................2.5 kV
RCM420-D-2
Rated insulation voltage .......................................................................................................................... 250 V
Overvoltage category/ pollution degree ...................................................................................................... III/3
Rated impulse voltage. .................................................................................................................................4 kV
Supply voltage
RCM420-D-1
Supply voltage range
U
s
..................................................................................... AC 24…60 V / DC 24…78 V
Operating range
U
s
............................................................................................ AC 16…72 V / DC 9.6…94 V
Frequency range
U
s
..................................................................................................................DC, 42…460 Hz
RCM420-D-2
Supply voltage range
U
s
..................................................................................................... AC/DC 100…250 V
Operating range
U
s
.............................................................................................................. AC/DC 70…300 V
Frequency range
U
s
....................................................................................................................... 42…460 Hz
Protective separation (reinforced insulation) between.................... (A1, A2) - (k/l, T/R) - (11, 12, 14) - (21, 22, 24)
Voltage test according to IEC 61010-1 .............................................................................................................. 2.21 kV
Power consumption ..........................................................................................................................................≤ 6.5 VA
Measuring circuit
External measuring current transformer ................................................................................. CTUB101-CTBC20…60
Rated insulation voltage (measuring current transformer) ................................................................................. 800 V
Frequency range ....................................................................................................................................... 0…2000 Hz
Measuring range AC ...................................................................................................................................... 0…1.5 A
Measuring range DC .................................................................................................................................. 0…600 mA