Error codes
Should, contrary to all expectations, a device error occur, error codes will ap-
pear on the display. Typical error codes are described below:
Error code
Meaning
E.01
Fault CT connection monitoring
Appropriate action:
Check CT connection for short-circuit or interruption.
After eliminating the fault, the error code will be auto-
matically deleted.
E.02
Fault CT connection monitoring
during manual self test.
Appropriate action:
Check CT connection for short-circuit or interruption.
After eliminating the fault and anew self-test or anew
device start and anew self-test or anew device start, the
error code will be automatically deleted.
E…
Error codes > 02 occurs:
Appropriate action:
Carry out a reset. Reset the device to factory setting.
After eliminating the fault, the error code will be auto-
matically deleted.
If the fault continues to exist, please contact the Bender
Service.