5.5.13 History memory query
The history memory can be selected via the menu HiS. Use the Up and Down
keys to view the next display. If Clr and M is flashing, the history memory can
be cleared by pressing the Enter key.
5.6
Commissioning
Prior to commissioning, check proper connection of the residual current mo-
nitor.
5.7
Factory setting
Response value I
Δ
n2
:
Response value I
Δ
n1
:
Hysteresis:
Fault memory M:
100% reference related to
the analogue interface:
start-up delay:
Password:
30 mA (I2)
50 % (I1)
15 %
activated
Response value I2
t = 0.5 s
0, deactivated (Off)