Operation and setting
29
RCMA420-DM_D00060_02_M_XXEN/06.2016
5.5.7
Setting the 100% reference related to the analogue
interface.
Set here whether the 100% value of the output signal is to be referred to res-
ponse value I2 (
I
Δn2
) (AL) or to a freely configurable value. Select the approp-
riate value from the range 10 mA…500 mA.
Factory setting = related to the response value I2 (
I
Δn2
) (AL).
The example below shows how to change the 100% reference of AL = related
to the response value to a 100% value of 60 mA.
3x
>1,5 s
5x