Overview Modbus registers (RCMS150-01 only)
32
RCMS150_D00259_01_M_XXEN/08.2021
Tab. 6.4: Error codes
6.4 Interface parameters
Tab. 6.5: Interface parameters
* The address is only used if both detent potentiometers are set to 0.
9.10
μC parameter
error
Parameters outside permissible
limits or error while saving.
Affected channel:
Gateway > Overview measur-
ing channels or Modbus regis-
ters 1004…1034 (5 = device
error)
Switch the device off and on again. Reset the cor-
responding channel to factory settings: via the
gateway or
Modbus registers 59013…59018.
If the error persists, return the device.
9.60
μC parameter
error
Parameter outside permissible
limits
Switch the device off and on again. Reset device
to factory settings: Modbus register 59020. If the
error persists, return the device.
9.70
μC task/ pro-
gramme
sequence
General software error
Switch the device off and on again.
If the error persists, return the device.
9.90
Error μC cycle
generation
Unacceptable deviation or fail-
ure of the μC cycle source.
Register
Property
Description
Format
Unit
Setting range
Factory setting
32000
RW
Modbus
address*
UINT16
—
1…247
The last two digits
of the serial number
+ 100
32001
RW
Modbus baud
rate
UINT32
Baud
1200 / 2400 /
4800 / 9600 /
19200 / 38400
/ 57600
19200
32003
RW
Modbus parity/
stop bit
UINT16
—
0 = 8N2
1 = 8O1
2 = 8E1
3 = 8N1
4 = 8O2
5 = 8E2
2 (8E1)
32004…32099
Reserved
Error
code
Error
Description
Action