Overview Modbus registers (RCMS150-01 only)
27
RCMS150_D00259_01_M_XXEN/08.2021
6.3 Measured values
Register Property
Description
Format
Comment/unit
01000
RO
Residual current measured value (K1 RMS) Float32
Current
instantaneous
value.
For status, refer to
Tab. 6.3
01002
RO
Residual current measured value (K1 DC)
Float32
01004
RO
Status K1
UINT32
01006
RO
Residual current measured value (K2 RMS) Float32
01008
RO
Residual current measured value (K2 DC)
Float32
01010
RO
Status K2
UINT32
01012
RO
Residual current measured value (K3 RMS) Float32
01014
RO
Residual current measured value (K3 DC)
Float32
01016
RO
Status K3
UINT32
01018
RO
Residual current measured value (K4 RMS) Float32
01020
RO
Residual current measured value (K4 DC)
Float32
01022
RO
Status K4
UINT32
01024
RO
Residual current measured value (K5 RMS) Float32
01026
RO
Residual current measured value (K5 DC)
Float32
01028
RO
Status K5
UINT32
01030
RO
Residual current measured value (K6 RMS) Float32
01032
RO
Residual current measured value (K6 DC)
Float32
01034
RO
Status K6
UINT32
01036
RO
Device error and
status information
Float32
If device errors are
present, the error
code is output here
with a factor of 100,
see Tab. 6.4.
If there are several
errors, the error
with the highest
error number is out-
put.
Example: 800 = 8.00
(hardware error)