![Bender LINETRAXX RCMS150 Manual Download Page 16](http://html.mh-extra.com/html/bender/linetraxx-rcms150/linetraxx-rcms150_manual_2731702016.webp)
Mounting, connection and commissioning
16
RCMS150_D00259_01_M_XXEN/08.2021
Meaning of the LEDs
Tab. 4.1: Description of the LEDs
4.3 Wiring diagram
LED
Meaning
ON
(green)
lights
Normal operation indicator
flashes quickly
RCMS150: Device error or BMS bus address set
incorrectly
flashes slowly
RCMS150-01: Device error
flashes very
quickly
RCMS150-01: Identify device (via Modbus RTU)
Flash code
Interface address output (see page 19)
ALARM K1…K6
(yellow)
lights
Main alarm (response value
I
Δn
exceeded)
flashes
Device error channel
Risk of short circuit!
Only insulated conductors with an insulation that is suitable for at least
the monitored voltage may be routed through the measuring current
transformer.
The rated voltage of the RCMS150… must not be exceeded.