Logging
78
PEM735_D00084_00_M_XXEN/02.2015
Tab. 8.3: Selectable measured quantities, data recorder
8.4 Energy log
The energy log stores the interval energy consumption for
Active energy import
Active energy export
Reactive energy import
Reactive energy export
Apparent energy
These measured values are stored in a non-volatile memory and will not suffer any
loss in the event of power failure. For the recording of the total energy values such
as
P
ges
or
Q
ges
the data recorder has to be used.
The programming of the energy log is only supported over communications.
The following set-up parameters are supported:
324
Active energy export
ges
kWh
325
Active energy
ges
kWh
326
Reactive energy import
ges
kvarh
327
Reactive energy export
ges
kvarh
328
Reactive energy
ges
kvarh
No.
Parameters
Setting
1
Recording mode
0 = disabled
1 = stop-when-full
2 = FIFO (First-In-First-Out)
2
Number of measure-
ments
0…65535 (entries)
3
Recording interval
0 = 5 min
1 = 10 min
2 = 15 min
3 = 30 min
4 = 60 min
4
Start time
yy/mm/dd, hh:mm:ss
Key
Measured quantities (data recorder)
Factor/unit
Summary of Contents for LINETRAXX PEM575 Series
Page 8: ......
Page 12: ...Making effective use of this document 12 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 28: ...Installation and connection 28 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 62: ...Application inputs and outputs 62 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 82: ...Logging 82 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 88: ...Power Quality 88 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 162: ...Modbus Register Map 162 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 166: ...Technical data 166 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 170: ...INDEX 170 PEM575_D00016_00_M_XXEN 04 2015 ...
Page 171: ......