Application/inputs and outputs
57
PEM735_D00084_00_M_XXEN/02.2015
7.5.1
Max/Min values per demand period
The PEM575 records the min and max values of the following measurements for
each demand period
three-phase voltages
three-phase currents
three-phase frequencies
three-phase power
three-phase power factors
λ
Voltage unbalance
Current unbalance
Total harmonic distortion, voltage (THD
U
)
Total harmonic distortion, current (THD
I
)
All recorded measuring values can be accessed via the communications interface.
7.6 Setpoints
The PEM575 features 24 user-programmable control setpoints (registers
6600…6839) which provide extensive control by allowing a user to initiate an ac-
tion in response to a specific condition. The alarm symbol
at the right side of
the LC display is lit if there are any active setpoints.
The first 16 setpoints (1…16) are
standard setpoints,
the other setpoints (17…24)
are
high-speed setpoints
.
Typical setpoint applications are alarming, fault location and power quality moni-
toring (PQ monitoring).
Setpoints can be programmed via the
communications interface.
The following
setup parameters
are provided:
1.
Setpoint type:
Specifies the monitoring condition (over setpoint or under
setpoint) or is disabled.
2.
Setpoint parameters
: Specifies the parameters to be monitored;
for standard setpoints all parameters are available, for high-speed setpoints
only the keys 1…14 apply.
Summary of Contents for LINETRAXX PEM575 Series
Page 8: ......
Page 12: ...Making effective use of this document 12 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 28: ...Installation and connection 28 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 62: ...Application inputs and outputs 62 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 82: ...Logging 82 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 88: ...Power Quality 88 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 162: ...Modbus Register Map 162 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 166: ...Technical data 166 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 170: ...INDEX 170 PEM575_D00016_00_M_XXEN 04 2015 ...
Page 171: ......