Application/inputs and outputs
56
PEM735_D00084_00_M_XXEN/02.2015
Demand period
(1…99 min)
Example of a total demand period
:
Demand cycles: 3
Demand period: 20 min
Total demand period: 3 x 20 min = 60 min
Predicted demand sensitivity SENS (70…99)
Values are determined for present demand and predicted demand
Voltages
(U
1
, U
2
, U
3
,
Ø
U
LN
, U
L1L2
, U
L2L3
, U
L3L1
,
Ø
U
LL
)
Currents (
I
1
,
I
2,
I
3
, Ø
I, I
4
)
Active power
P (P
1
, P
2
, P
3
, P
ges
)
Apparent power
S (S
1
, S
2
, S
3
, S
ges
)
Reactive power
Q (Q
1
, Q
2
, Q
3
, Q
ges
)
Power factor
λ
(
λ
1
,
λ
2
,
λ
3
,
λ
ges
)
Frequency
Voltage unbalance
Current unbalance
Total harmonic distortion, voltage
(THD
U1
, THD
U2
, THD
U3
)
Total harmonic distortion, current
(THD
I1
, THD
I2
, THD
I3
)
The demand period can be set using the buttons on the front panel or via the com-
munications interface. The following options are available:
1, 2, 3, 5, 10, 15, 30, 60 minutes
In addition to the demand period also the demand cycles (sliding window) bet-
ween 1 and 15 are to be specified.
During the total demand period (duration multiplied by the number), the con-
sumption resp. the imported power is measured. Then the
average demand value
is indicated on the display
and output via the communications interface.
The maximum demand value (peak demand) determined over the whole recording
period will be saved and displayed. The peak demand can be reset manually.
Setting possibilities: Chapter 6.9 Setup: adjustment possibilities.
Summary of Contents for LINETRAXX PEM575 Series
Page 8: ......
Page 12: ...Making effective use of this document 12 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 28: ...Installation and connection 28 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 62: ...Application inputs and outputs 62 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 82: ...Logging 82 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 88: ...Power Quality 88 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 162: ...Modbus Register Map 162 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 166: ...Technical data 166 PEM735_D00084_00_M_XXEN 02 2015 ...
Page 170: ...INDEX 170 PEM575_D00016_00_M_XXEN 04 2015 ...
Page 171: ......