Operation
47
CMS460-D_D00045_01_M_XXEN/07.2016
6.4.6.1
Settings menu 1: General
In this menu you make settings that apply to this device and therefore to all
measuring channels.
1.Fault memory
Faults that only occur temporarily can be saved.
on
After eliminating the cause of fault all alarm messages re-
main stored until a reset is carried out.
off
CMS460-D exits the alarm mode as soon as the cause of fault
is eliminated.
2.Prewarning
Setting as a percentage of the response value. Setting range: 10…100 %, res-
olution of setting 1 %.
3.Hysteresis
If the measured value is relatively close to the response value, the CMS460-D
would constantly switch between the alarm and normal states. If a hysteresis
of 20 % is set, the alarm status is not exited until the measured value is 20 %
below or above the response value. Setting range: 2…40 %, resolution of set-
ting 1 %.
10.Clock
Set date format, date, time and summer
time changeover.
11.Password
Changing and activating the password.
12.Factory set-
ting
Resets all settings to factory settings.
13.Service
For Bender service only.
Menu item
Function
Page
Summary of Contents for LANTRAXX CMS460-D
Page 6: ......
Page 21: ...Installation and connection 21 CMS460 D_D00045_01_M_XXEN 07 2016 4 3 2 Wiring diagram ...
Page 26: ...Installation and connection 26 CMS460 D_D00045_01_M_XXEN 07 2016 ...
Page 28: ...Installation and connection 28 CMS460 D_D00045_01_M_XXEN 07 2016 ...
Page 66: ...Operation 66 CMS460 D_D00045_01_M_XXEN 07 2016 ...
Page 70: ...Tests service troubleshooting 70 CMS460 D_D00045_01_M_XXEN 07 2016 ...
Page 85: ......
Page 86: ......
Page 87: ......