Commissioning
30
CMS460-D_D00045_01_M_XXEN/07.2016
5.2
Switching on
1. Connect the supply voltage of all devices connected to the BMS bus.
Initially, the "ON" LED flashes on the CMS460-D and the graphic display
shows the (Bender) welcome screen. The "ON" LED then lights up per-
manently.
2. Set the BMS bus addresses. Never assign one address twice. Check, if
address 001 and thus the master function has been assigned.
3. Select the appropriate national language English, German or French
(see page 59).
4. Set the CT type for each channel, see page 55
5. Start the preset function (see page 48).
6. Switch off unassigned measuring channels to avoid device errors (see
7. If a response value is exceeded or device error messages occur, this is
indicated on the CMS460-D by illuminated alarm LEDs and a respective
message on the graphic display. You can find information about the
alarms on the CMS460-D in the "Alarm/meas.value" menu.