Technical data
Technical data
isoPV1685xxx_D00007_05_M_XXEN/02.2020
33
Connection (except system coupling)
Connection type....................................................................................................................................... pluggable push-wire terminals
Connection, rigid/flexible............................................................................................................................ 0.2...2.5 mm
2
/0.2...2.5 mm
2
Connection, flexible with ferrule, without/with plastic sleeve........................................................................................ 0.25...2.5 mm
2
Conductor sizes (AWG) .................................................................................................................................................................24…12
Connection of the system coupling
Connection type....................................................................................................................................... pluggable push-wire terminals
Connection, rigid/flexible................................................................................................................................ 0.2...10 mm
2
/0.2...6 mm
2
Connection, flexible with ferrule, without/with plastic sleeve ................................................................... 0.25...6 mm
2
/0.25...4 mm
2
Conductor sizes (AWG) .................................................................................................................................................................. 24…8
Stripping length.............................................................................................................................................................................. 15 mm
Opening force ......................................................................................................................................................................... 90…120 N
Environment/EMC
EMC ........................................................................................................................................................................ IEC 61326-2-4 Ed. 1.0
Classification of climatic conditions acc. to IEC 60721:
Without solar radiation, precipitation, water, icing. Condensation possible temporarily:
Stationary use (IEC 60721-3-3) ...........................................................................................................................................................3K5
Transport (IEC 60721-3-2)..................................................................................................................................................................2K11
Long-term storage (IEC 60721-3-1) ................................................................................................................................................. 1K22
Classification of mechanical conditions acc. to IEC 60721:
Stationary use (IEC 60721-3-3)...........................................................................................................................................................3M4
Transport (IEC 60721-3-2).................................................................................................................................................................. 2M4
Long-term storage (IEC 60721-3-1) ............................................................................................................................................... 1M12
Deviation from the classification of climatic conditions:
Ambient temperature during operation .......................................................................................................................... –40…+70 °C
Ambient temperature transport ....................................................................................................................................... –40…+80 °C
Ambient temperature long-term storage ...................................................................................................................... –25 …+80 °C
Relative humidity .................................................................................................................................................................. 10…100 %
Atmospheric pressure................................................................................................................... 700...1060 hPa (max. height 4000 m)
Other
Operating mode ...................................................................................................................................................... continuous operation
Position of normal use............................................................................................................................ vertical, system coupling on top
PCB fixation................................................................................................................................................... lens head screw DIN7985TX
Tightening torque............................................................................................................................................................................ 4.5 Nm
Degree of protection, internal components........................................................................................................................................ IP30
Degree of protection, terminals .......................................................................................................................................................... IP30
Weight ........................................................................................................................................................................................ ≤ 1300 g
( )* = factory settings
11.2 Standards, approvals and certifications
The isoPV1685 was designed according to the following standards:
•
DIN EN 61557-8 (VDE 0413-8)
•
IEC 61557-8
•
IEC 61557-9
•
IEC 61326-2-4
•
IEC 60730-1
•
DIN EN 60664-1 (VDE 0110-1)
•
UL1998 (software) (isoPV1685RTU only)
11.3 Ordering details
The data labelled with an * are absolute values
Type
Response value
range
Supply voltage *
Art. No.
isoPV1685RTU-425
200 Ω
…
1 MΩ
DC 18
…
30 V
B91065603
isoPV1685P-425
200 Ω
…
1 MΩ
DC 18
…
30 V
B91065604
for isoPV1685RTU only