59
isoPV_D00024_02_M_XXEN/07.2018
9. Technical data isoPV with AGH-PV
9.1 Data in tabular form isoPV
The values marked with** are absolute values.
()* = factory setting
Insulation coordination acc. to IEC 60664-1
Definitions:
Supply circuit (IC2) ................................................................................................................................................... A1, A2
Output circuit (IC3)............................................................................................................................................... 11, 14, 24
Control circuit (IC4) .........................................................................................................Up, KE, T/R, A, B, AK1, GND, AK2
Rated voltage .......................................................................................................................................................................240 V
Overvoltage category................................................................................................................................................................. III
Rated impulse voltage:
IC2/(IC3-4)...................................................................................................................................................................... 4 kV
IC3/(IC4) ......................................................................................................................................................................... 4 kV
Rated insulated voltage:
IC2/(IC3-4).................................................................................................................................................................... 250 V
IC3/(IC4) ....................................................................................................................................................................... 250 V
Polution degree.......................................................................................................................................................................... 3
Protective separation (reinforced insulation) between:
IC2/(IC3-4)........................................................................................................................... Overvoltage category III, 300 V
IC3/(IC4) .............................................................................................................................. Overvoltage category III, 300 V
Voltage test (routine test) according to IEC 61010-1:
IC2/(IC3-4).............................................................................................................................................................. AC 2.2 kV
IC3/(IC4) ................................................................................................................................................................. AC 2.2 kV
Voltage ranges
Nominal system voltage
U
n
..................................................................................................................................... via AGH-PV
isoPV-335:
Supply voltage
U
s
(also see nameplate) ........................................................................................................ AC 88…264 V**
Frequency range
U
s
................................................................................................................................................ 42…460 Hz
Power consumption ...................................................................................................................................................
≤
21,5 VA
Supply voltage
U
s
(also see nameplate) ........................................................................................................ DC 77…286 V**
Power consumption .....................................................................................................................................................
≤
5,5 VA
isoPV-327:
Supply voltage
U
s
(also see nameplate) ....................................................................................................... AC 19.2…55 V**
Frequency range
U
s
................................................................................................................................................ 42…460 Hz
Summary of Contents for ISOMETER isoPV with AGH-PV
Page 45: ...Operation and setting 45 isoPV_D00024_02_M_XXEN 07 2018 6 5 8 Diagram ISO ADVANCED ...
Page 47: ...Operation and setting 47 isoPV_D00024_02_M_XXEN 07 2018 6 6 4 Diagram COM SETUP ...
Page 57: ...57 isoPV_D00024_02_M_XXEN 07 2018 ...
Page 58: ...Coupled PV generators application example 58 isoPV_D00024_02_M_XXEN 07 2018 ...
Page 71: ......