
Technical data isoLR275 with AGH-LR
69
isoLR275_D00127_00_M_XXEN/07.2018
7.4
Characteristic curves
Current output 0…20 mA
R
F
= Insulation fault in kΩ
R
Sk
= Centre scale in kΩ
I
= Current output in mA
1,00
10,00
100,00
1000,00
0,0
5,0
10,0
15,0
20,0
25,0
I[mA]
R
F
[k
]
Rsk=28kOhm
Rsk=120kOhm
R
F
=
20 mA x R
Sk
I
- R
Sk