Operation and configuration
49
isoLR275_D00127_00_M_XXEN/07.2018
5.6
Menu COM SETUP: Setting the BMS interface
5.6.1
Bus address "Addr:"
This menu is used to set the BMS bus address for isoLR275. Take care that the
bus address is not assigned twice.
The device is factory set to address 3 and hence operates as a slave.
5.6.2
ISOnet function
The ISOnet function can be set in the COM SETUP menu under ISOnet = ON.
The ISOnet function of all ISOMETER®s existing in the system must be set to
"ON". The BMS master with activated ISOnet function controls the ISOnet sla-
ve devices via the BMS bus. When the master ISOMETER® has finished one
measuring cycle, the authorisation for insulation monitoring is passed on to
the next slave device. During the insulation monitoring process, all other
ISOMETER®s are in the STANDBY mode.
If several isoLR275s are operated on one BMS bus, the address of
other ISOMETER®s must be assigned one after the other, since
only one device may have the master function.