isoHV525-S4-4 parameter overview
29
isoHV525_D00297_04_M_XXEN/05.2018
5.5 Function configuration
FAC
= Factory setting;
Cs
= Customer setting
5.6 Measured value description
Para-
meter
Activation
Description
Available via
FAC
Cs
BMS Modbus
nEt
on
Test system connection during device test
X
X
S.Ct
on
Device test during device start
X
Description
Insulation resistance
R
F
1 kΩ ... 4 MΩ Resolution 1 kΩ
System leakage capacitance
C
e
1
μF
... 200
μF
Resolution 1
μF
Nominal system voltage L1 - L2
U
n
0 V
RMS
…1.15k V
RMS
Resolution 1 V
RMS
Residual voltage L1/+ - PE
U
L1e
0 V
DC
…1.15k V
DC
Resolution 1 V
DC
Residual voltage L2/-
- PE
U
L2e
0 V
DC
…1.15k V
DC
Resolution1 V
DC
Fault location in %
-100 % …+100 %
Insulation resistance
R
UGe
1 kΩ ... 4 MΩ Resolution 1 kΩ